| 2001-07-04 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01060851 |
| | 901 S FLAGLER # 2237 |
| | CONT: ABBOTT & PURDY |
| | PHONE: 655-6662 |
| | NOTE: |
| | BUSINESS OCCUPANCY: 1020.1 SINGLE EXIT- |
| | 2 STORY MAX, UNDER 3500 SQ FT, < 40 |
| | PEOPLE AND TRAVEL DISTANCE < 75". |
| | |
| | 1)- INFORMATION ON THE EGRESS DOOR IS |
| | MISSING, A KEYED LOCKING DEVISE MAY BE |
| | USED, THEN A SIGN ON THE DOOR STATING: |
| | THIS DOOR TO REMAIN UNLOCKED WHEN THIS |
| | BUILDING IS OCUPIED. |
| | |
| | 2)- THE PLANS INDICATE THAT THERE IS TO |
| | BE SOME TYPE OF GASSES USED BUT THE TYPE |
| | OF GASSES AND QUANITIES ARE NOT GIVEN. |
| | SBC 308.2.2 ALLOWS FOR CONTROL AREAS OF |
| | HAZARDOUS MATERIALS NOT EXCEEDING THE |
| | EXEMPT QUANITITIES SHALL BE PERMITTED IN |
| | ALL OCCUPANCIES EXCEPT ASSEMBLY OCCUPAN- |
| | CIES. THE CONTROL AREA SHALL BE SEPER- |
| | ATED BY AN 1 HR FIRE RESISTANT CONSTRUC- |
| | TION WITH 3/4 HR RATED OPENING PROTECT- |
| | TION WITH SELF CLOSING OR AUTOMATIC |
| | CLOSING DEVISES IN ACCORDANCE WITH |
| | 705.1.3.2.3. THE MAXIMUM NUMBER OF |
| | CONTROL AREAS PER FLOOR IN MULTISTORY |
| | BUILDINGS SSHALL BE LIMITED TO FOUR.SEE |
| | TABLES TABLE 308: 2A-2D. |
| | |
| | SBC 407.1.3.5: LABORATORY FUME HOODS |
| | WHERE FLAMMABLE MATERIALS ARE USED SHALL |
| | BE PROTECTED BY AN AUTOMATIC SPRINKLER |
| | SYSTEM. |
| | |
| | PLEASE PROVIDE THE DISTRIBUTED LIVE LOAD |
| | USED IN THIS ROOM. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 EX 8412 |