| Date |
Text |
| 2001-08-31 00:00:00 | ************BUILDING PROVISO************ |
| | |
| | 1)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - GARAGE DOORS (PRIOR TO INSTALLATION) |
| | |
| | 2) STRUCTURE IS LOCATED IN AN AO FLOOD |
| | ZONE AN ELEVATION CERTIFICATE IS |
| | REQUIRED. |
| | |
| | 3) IF OPTIONS ARE USED, THE CORRESPOND- |
| | ING PRODUCT APPROVALS MUST BE SUBMITTED. |
| | MANUFACTURER'S SPECIFICATIONS AND LIST- |
| | ING INFORMATION IS REQUIRED IF OPTIONAL |
| | BBQ IS INSTALLED. |
| | |
| | 4) PROVIDE PRODUCT APPROVALS, KEY PLAN |
| | AND INSTALLATION SCHEDULE FOR STORM |
| | PANELS UNDER A SEPARATE PERMIT. |
| | |
| | |
| | TRUSSES |
| | UNSAT |
| | |
| | 1) THE TRUSS ENGINEERS TITLE BLOCK (NAME |
| | ADDRESS AND NUMBER) IS REQUIRED ON THE |
| | TRUSS LAYOUT. |
| | |
| | 2) THE TRUSS DRAWINGS REFERENCE |
| | INCORRECT DESIGN CRITERIA (ASCE 7-93), |
| | THE PROPER CRITERIA IS ASCE 7-95 WITH |
| | (145 MPH WINDLOAD) OR 1997 SBC SECTION |
| | 1606 WITH (110 MPH WINDLOAD). PLEASE |
| | CORRECT. |
| | |
| | 3) THE TRUSS DETAILS FOR BRACING, GABLES |
| | OVERHANG, PIGGYBACKS, ETC. |
| | |
| | 4) TRUSS DRAWINGS TG33, T34 AND T35 ARE |
| | NOT SHOWN ON THE TRUSS LAYOUT AND THERE |
| | ARE NO TRUSS DRAWINGS FOR TRUSSES TG31, |
| | T32 AND T33 WHICH ARE INDICATED ON THE |
| | TRUSS LAYOUT. PLEASE CORRECT. |
| | |
| | 5) THERE ARE TWO TRUSS DRAWINGS FOR THE |
| | SAME TRUSS WITH DIFFERENT UPLIFT VALUES |
| | LISTED. PLESAE CORRECT. |
| | |
| | NOTE: |
| | THESE COMMENTS APPLY TO THE FOLLOWING |
| | PERMIT NUMBERS: 01060846, 01060847, |
| | 01060848, 01060849. |