2001-07-05 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01060807
 ONE N. CLEMATIS # 3 RD FL
 QUEST
 PHONE # 691-9400
  
 1)- OFFICE SPACE DOESN'T MEET THE RE-
 QUIEMENTS FOR A SINGLE MEANS OF EGRESS.
 SBC 1020.1 (1-4) THIS SPACE DOESN'T MEET
 REQUIREMENT 1&4. 1)- BEING THE MAXIMUM
 2 STORIES (BUILDING) IN HEIDTH. 2ND)
 THE MAXIMUM DISTANCE OF TRAVEL TO THE
 EXIT DOES NOT EXCEED 75'.
  
 2)- SINCE THE OFFICE REQUIRES THE (2)
 EXITS SBC 1004.1.4 REQUIRES THAT THE 2
 EXITS OR EXIT ACCESS DOORS SHALL BE
 PLACED A DISTANCEAPART EQUAL TO NOT
 LESS THAN ONE HALF OF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF
 THE OFFICE. DIAGONAL DISTANCE OF 81'-0".
 81'X 1/2= 40.5' APART. THE PLANS INDI-
 CATE APPROXIMATELY 31'.
  
 3)- DOORS 301 & 307B DO NOT GIVE WHAT
 RATING THEY HAVE? SBC T-705.1.2.
  
 4)- SBC 803.2/ 803.3(TABLE) PLEASE INDIC
 ATE THE MINIMUM INTERIOR FINISH CLASSIFI
 CATION, FLAMESPREAD & SMOKE DEVELOPMENT.
  
 5)- SHEET A-3 FINISH NOTESFOR FLOORS:
 FL ACCEC CODE 4.3.8 CHANGE IN GRADE,
 NOTE 1/4" IN VETICAL CHANGE IN GRADE,
 1/2" IF GRADE HAS A 2/1 RATIO.
  
 6)- FL ACC CODE 4.3.6 SURFACE TEXTURES
 FLOOR SURFACES ALONG THE ACCESSIBLE PATH
 SHALL BE STABLE, FIRM & SLIP RESISTANT.
 (ADDAAG) A-5 A SATATIC COEFIFICIENT OF
 FRICTION OF0.6 ACCESSIBLE ROUTE, 0.8
 ACCESSIBLE ROUTE FOR RAMPS.
  
 BUILDING PLAN REVIEW