| 2001-06-25 00:00:00 | FAILED.. |
| | |
| | 1) SHOW LOCATION OF DISHWASHER. LOCAL |
| | ORD. 2839-96. DISHWASHER TO SANT. SEWER. |
| | |
| | 2) GREASE TRAP SIZE AND LOCATION TO BE |
| | APPROVED BY RODNEY COMPO OF THE UTILITY |
| | DEPARTMENT. (561) 837-4074 |
| | |
| | 3) SEPARATE PERMIT FOR GREASE TRAP, |
| | ISSUED TO PROVIDER OF GREASE TRAP. |
| | |
| | 5) PAGE 1.0, EQUIPMENT LIST DOES NOT |
| | MATCH EQUIPMENT FLOOR PLAN. |
| | |
| | 6) TWO WAY CLEAN OUTS REQUIRED OUTSIDE |
| | OF BUILDING LINE IN BOTH SANITARY AND |
| | GREASE LINES EXITING THE BLDG. |
| | |
| | 7) SHUT OFF VALVES FOR MENS ROOM NOT |
| | SHOWN ON WATER RISER DIAGRAM. PAGE 3.0 |
| | |
| | 8) SHOW WATER HEATER DETAIL AND LOCATION |
| | |
| | 9) MENS AND WOMENS RESTROOMS ARE NOT |
| | LARGE ENOUGH. PER TABLE 407, TWO W/C'S |
| | AND TWO LAVS ARE REQUIRED FOR 65 PERSONS |
| | HANDICAP STALL REQUIRED IN EACH REST- |
| | ROOM. A URNAL IN REQUIRED IN MENS' REST- |
| | ROOM. |
| | |
| | 10) IRRIGATION PERMIT REQUIRED. WATER |
| | SUPPLY BY PLUMBING CONTRACTOR. |
| | |
| | 11) PAGE 3.0 PLUMBING NOTES #8, PIPING |
| | 2" AND SMALLER TO HAVE 1/4" PER FOOT |
| | FALL PER SPC-94 SEC 705.2 |
| | |
| | 12) PAGE 3.0 PLUMBING NOTES #12, AIR- |
| | CHAMBERS TO BE ACCESSABLE AND RECHARGE- |
| | ABLE PER SPC-94 607.8.2 & 607.8.3 |
| | APPROVED MECHANICAL WATER HAMMER ARREST- |
| | ORS TO BE INSTALLED PER MANUFACTURE IN- |
| | STRUCTIONS. |
| | |
| | 13) SEPARATE GAS PERMIT REQUIRED. |
| | GAS PERMIT APPLICATION REQUIREMENT SHEET |
| | INFORMATION TO BE SUBMITTED. PLEASE ADD- |
| | RESS ALL CIRCLED SECTIONS. |
| | PLEASE SUBMIT A COPY OF APPROPRIATE GAS |
| | SIZING CHART FROM SGC-97 (305.4A). |
| | ALSO SUBMIT MANUFACTURE SHEETS FOR ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA, 54 AND THE STANDARD GAS |
| | CODE. 1" PIPE AT 66 TOTAL DEVELOPED |
| | LENGTH IS NOT LARGE ENOUGH TO DELIVER |
| | 351,000 BTU, 1-1/4" WILL BE REQUIRED. |
| | |
| | 14) GAS RISER DETAIL PAGE 3.0 SHOWS |
| | UNIONS BEFORE SHUT OFF VALVES AT THE |
| | EMERGENCY SHUT OFF. THE VALVES SHOULD |
| | BE OUTSIDE OF THE UNIONS TO SERVICE |
| | THE VALVE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT. 8377 |