| Plan Review Notes For Permit 01060797 |
| Permit Number |
01060797 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-10 00:00:00 | *******************DENIED*************** | | | | | | | | | | | | PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2. | | | | | | PROVIDE INFORMATION ON EXHAUST FANS FOR | | | GREASE HOOD. | | | | | | ADDITIONAL PERMITS REQUIRED FOR GREASE | | | HOOD SYSTEM, FIRE SUPRESSION AND | | | WALK-IN COOLERS.PLEASE PROVIDE | | | MAUFACTURER SUBMITTAL DATA AND PLANS | | | WITH PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|