Plan Review Notes
Plan Review Notes For Permit 01060797
Permit Number 01060797
Review Stop E
Sequence Number 1
Notes
Date Text
2001-06-24 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT BOTH EXISTING/
 AND NEW PANELS ARE SHOWN W/OUT HAVING
 MAINS? PLEASE NOTE NO MAIN IS SHOWN
 OUTSIDE? SOME FORMOF MAIN IS REQ`D PER
 225-31/225-32
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE SANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372