| Plan Review Notes For Permit 01060797 |
| Permit Number |
01060797 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-24 00:00:00 | *************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT BOTH EXISTING/ | | | AND NEW PANELS ARE SHOWN W/OUT HAVING | | | MAINS? PLEASE NOTE NO MAIN IS SHOWN | | | OUTSIDE? SOME FORMOF MAIN IS REQ`D PER | | | 225-31/225-32 | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE SANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|