2001-07-05 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01060797
 2200 S DIXIE HWY
 L. DAVIS CONSTRUCTION
 P: 848-0577
 F: 848-0954
 C: 718-8161
  
 1)- SBC REQUIRES THAT THE RESTROOM WALLS
 & FLOOR TO BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4 FT ABOVE THE
 FINISH FLOOR.
  
 2)- SBC 803.3.1 INTERIOR FINISH SCHEDULE
 BASED ON OCCUPANCY, TABLE 803.3.
 FLAMESPREAD & SMOKE DEVELOPMENT.
  
 3)- FL 1997 ACCESSIBILITY CODE 4.5.1:
 GROUND AND FLOOR SURFACES ALONG ACCESSIB
 LE ROUTES AND IN ACCESIBLE ROOMS &
 SPACES INCLUDING FLOORS RAMPS SHALL BE
 FIRM, SLIP-RESISTANT. A STATIC COEFIC-
 IENT OF FRICTION OF 0.6 IS RECOMMENDED
 FOR ACCESSIBLE ROUTES AND 0.8 FOR RAMPS.
  
 4)- FL ACC CODE REQUIRES 36" CLEAR
 ACCESS ISLES, SBC T-1004 REQUIRES CLEAR
 ISLE WIDTH OF 44" WITH AN OCCUPANT LOAD
 OF 50 OR >.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412