| Plan Review Notes For Permit 01060797 |
| Permit Number |
01060797 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-05 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01060797 | | | 2200 S DIXIE HWY | | | L. DAVIS CONSTRUCTION | | | P: 848-0577 | | | F: 848-0954 | | | C: 718-8161 | | | | | | 1)- SBC REQUIRES THAT THE RESTROOM WALLS | | | & FLOOR TO BE LINED WITH NONABSORBANT | | | MATERIALS TO A HEIGTH OF 4 FT ABOVE THE | | | FINISH FLOOR. | | | | | | 2)- SBC 803.3.1 INTERIOR FINISH SCHEDULE | | | BASED ON OCCUPANCY, TABLE 803.3. | | | FLAMESPREAD & SMOKE DEVELOPMENT. | | | | | | 3)- FL 1997 ACCESSIBILITY CODE 4.5.1: | | | GROUND AND FLOOR SURFACES ALONG ACCESSIB | | | LE ROUTES AND IN ACCESIBLE ROOMS & | | | SPACES INCLUDING FLOORS RAMPS SHALL BE | | | FIRM, SLIP-RESISTANT. A STATIC COEFIC- | | | IENT OF FRICTION OF 0.6 IS RECOMMENDED | | | FOR ACCESSIBLE ROUTES AND 0.8 FOR RAMPS. | | | | | | 4)- FL ACC CODE REQUIRES 36" CLEAR | | | ACCESS ISLES, SBC T-1004 REQUIRES CLEAR | | | ISLE WIDTH OF 44" WITH AN OCCUPANT LOAD | | | OF 50 OR >. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|