| Plan Review Notes For Permit 01060623 |
| Permit Number |
01060623 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-15 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | 1) | | | | | | 2)NOTE: PLEASE NOTE PLAN WERE NOT SUB- | | | -MITTED COMPLETE. NO LOAD CALCULATIONS, | | | NO SERVICE FEEDER SIZES, NO PANEL SCHEDU | | | LES THAT CORRELATE WITH BRANCH CIRCUITS | | | SHOWN ON PLANS. | | | 3) NOTE: PLEASE SHOW ALL CONTINUOUS AT | | | 125%. (LIGHTING ETC) | | | | | | 3)NOTE: PLEASE SHOW SIZES FOR ALL | | | EQUIPMENT. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REIVEW | | | 561-659-8099 EXT 8372 |
|