Plan Review Notes
Plan Review Notes For Permit 01060623
Permit Number 01060623
Review Stop E
Sequence Number 1
Notes
Date Text
2001-06-15 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 1)
  
 2)NOTE: PLEASE NOTE PLAN WERE NOT SUB-
 -MITTED COMPLETE. NO LOAD CALCULATIONS,
 NO SERVICE FEEDER SIZES, NO PANEL SCHEDU
 LES THAT CORRELATE WITH BRANCH CIRCUITS
 SHOWN ON PLANS.
 3) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
  
 3)NOTE: PLEASE SHOW SIZES FOR ALL
 EQUIPMENT.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REIVEW
 561-659-8099 EXT 8372