| Date |
Text |
| 2001-06-24 00:00:00 | ******************* UNSAT ************* |
| | |
| | 1)NOTE: PLEASE NOTE THAT PLANS ARE |
| | SHOWING SM APPLIANCE CIRCUTIS AT 5000W`S |
| | PLEASE NOTE THAT SM APPL IS REQ`D AT |
| | 1500KW PER CIRCUIT. PLEASE CORRECT |
| | |
| | 2)NOTE: PLEASE NOTE THAT LOAD SHOWN FOR |
| | GARAGE DOOR OPENERS EXCEED 80% OF 15A |
| | BRKR. |
| | |
| | 3)NOTE: PLEASE NOTE THAT PLANS SHOW WELL |
| | PUMP AND PANEL SCHEDULE SHOWS SPRINKLER |
| | VALVE. PLEASE CLARIFY. |
| | |
| | 4)NOTE: PLEASE NOTE THAT THE GFI NOTE |
| | ON PLANS IN REF TO GFI`S IN KITCHEN IS |
| | NO LONGER.(93 NEC). PLEASE NOTE THAT ALL |
| | RECEPTS SERVING KITCHEN COUNTERSPACE ARE |
| | TO BE GFI/GFI PROTECTED. PER 210-8-A-6. |
| | |
| | 5) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 7)NOTE: PLEASE NOTE THAT RISER IS SHOWIN |
| | G AN EQUIPMENT GROUNDING CONDUCTOR |
| | BETWEEN METER AND FIRST MEANS OF DISCO- |
| | -NNECT. PLEASE NOTE THAT THIS WOULD BE |
| | PARALLELING THE NEUTRAL. |
| | |
| | 8) PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.1 |
| | MECHANICAL CODE. |
| | |
| | 9)NOTE: PLEASE NOTE THAT PLANS ARE SHOW- |
| | -ING TWO METERS? PLEASE CLARIFY. |
| | IS SECOND LOCATION OPTIONAL? |
| | |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |