| 2001-06-19 00:00:00 | ****************** UNSAT *************** | | | | | | | | | 1) PLEASE NOTE EITHER MISSING EGRESS | | | LIGHTING AND/OR CLARIFY EGRESS LIGHTING | | | PER 210-70 OF THE NEC. | | | PLEASE NOTE NUMEROUS ROOMS MISSING | | | EGRESS LIGHTING. | | | | | | 2)NOTE: PLEASE NOTE THAT ELECTRICAL NOTE | | | -S ON PLANS REFERENCE ART 251-22 FOR | | | GROUNDING. PLEASE NOTE THAT THIS MUST BE | | | A MISPRINT. PLEASE CHANGES THE ART IS | | | 250-122 NEC. | | | | | | 3)NOTE: PLEASE NOTE PANEL SCHEDULE "A" | | | PLEASE NOTE THAT OCP/BRKR AND WIRE | | | SIZES NEED TO CORRELATE. PLEASE NOTE | | | THAT YOU SHOW 30A OCP W/ 7000W LOAD? | | | AND 50A OCP ON 5000W LOAD? PLEASE ALSO | | | NOTE THAT 1- 20A OCP W/ 8OOOW LOAD. | | | PLEASE CORRECT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|