Plan Review Notes
Plan Review Notes For Permit 01060525
Permit Number 01060525
Review Stop R
Sequence Number 1
Notes
Date Text
2001-06-29 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 3) THE ROOF FRAMING PLAN LOCATED ON
 SHEET 3 IS A REVERSE OF THE OTHER
 DRAWINGS SUBMITTED. PLEASE CORRECT.
  
 4) DETAIL A ON SHEET 3 IS NOT SHOWN.
  
 5) PROVIDE DETAIL OF THE CANTILEVERED
 CONCRETE BEAM REINFORCEMENT AT THE LANAI
  
 TRUSSES
 UNSAT
  
 1) THE MEAN ROOF HEIGHT GIVEN ON THE
 TRUSS DRAWINGS IS NOT CONSISTENT. PLEASE
 CORRECT. MEAN ROOF HEIGHT OF THE
 STRUCTURE IS 15FT.
  
 2) DESIGN CRITERIA ON PLANS LISTS 97
 SBCCI, THE ORGANIZATION AND NOT THE 97
 SBC, THE CODE. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202