| Plan Review Notes For Permit 01060525 |
| Permit Number |
01060525 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-29 00:00:00 | *************BUILDING UNSAT************* | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) STRUCTURE IS LOCATED IN AN "A" FLOOD | | | ZONE AN ELEVATION CERTIFICATE WILL BE | | | REQUIRED. | | | | | | 3) THE ROOF FRAMING PLAN LOCATED ON | | | SHEET 3 IS A REVERSE OF THE OTHER | | | DRAWINGS SUBMITTED. PLEASE CORRECT. | | | | | | 4) DETAIL A ON SHEET 3 IS NOT SHOWN. | | | | | | 5) PROVIDE DETAIL OF THE CANTILEVERED | | | CONCRETE BEAM REINFORCEMENT AT THE LANAI | | | | | | TRUSSES | | | UNSAT | | | | | | 1) THE MEAN ROOF HEIGHT GIVEN ON THE | | | TRUSS DRAWINGS IS NOT CONSISTENT. PLEASE | | | CORRECT. MEAN ROOF HEIGHT OF THE | | | STRUCTURE IS 15FT. | | | | | | 2) DESIGN CRITERIA ON PLANS LISTS 97 | | | SBCCI, THE ORGANIZATION AND NOT THE 97 | | | SBC, THE CODE. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|