| Notes |
| Date |
Text |
| 2001-06-13 00:00:00 | 1) FIRE HYDRANTS ARE TO BE SPACED | | | BETWEEN 300-500 FEET APART. | | | 2) ALL UNDERGROUND FIRE LINES ARE TO | | | BE LISTED FOR FIRE PROTECTION SERVICE. | | | 3) ALL UNDERGOUND FIRE LINES AND THEIR | | | APPURTENANCES ARE TO MEET THE | | | REQUIREMENTS OF NFPA 24. | | | 4) ALL UNDERGROUND FIRE LINES ARE TO | | | BE PRESSURE TESTED AND INSPECTED BY | | | CITY OF WEST PALM BEACH OFFICIALS. | | | 5) PER CITY CODE SECTION 11-4 NO OBJECTS | | | ARE TO BE PLACED WITHIN 18 FEET OF ANY | | | FIRE HYDRANT. | | | 6) WET FIRE HYDRANTS ARE TO BE PROVIDED | | | PRIOR TO, DURING AND AFTER CONSTRUCTION. | | | 7) TAMPER SWITCHES, CHAINS AND LOCKS ARE | | | TO BE PROVIDED FOR BACKFLOW DEVICE. | | | 8) SUITABLE ROADS ARE TO BE PROVIDED | | | DURING CONSTRUCTION FOR FIRE AND | | | PARAMEDICAL ACCESS. | | | 9) FIRE DEPARTMENT CONNECTIONS FOR THE | | | APARTMENT BUILDINGS ARE TO BE NO MORE | | | THAN 150 FEET FROM NEARBY FIRE HYDRANTS. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|