Plan Review Notes
Plan Review Notes For Permit 01060486
Permit Number 01060486
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-06-13 00:00:001) FIRE HYDRANTS ARE TO BE SPACED
 BETWEEN 300-500 FEET APART.
 2) ALL UNDERGROUND FIRE LINES ARE TO
 BE LISTED FOR FIRE PROTECTION SERVICE.
 3) ALL UNDERGOUND FIRE LINES AND THEIR
 APPURTENANCES ARE TO MEET THE
 REQUIREMENTS OF NFPA 24.
 4) ALL UNDERGROUND FIRE LINES ARE TO
 BE PRESSURE TESTED AND INSPECTED BY
 CITY OF WEST PALM BEACH OFFICIALS.
 5) PER CITY CODE SECTION 11-4 NO OBJECTS
 ARE TO BE PLACED WITHIN 18 FEET OF ANY
 FIRE HYDRANT.
 6) WET FIRE HYDRANTS ARE TO BE PROVIDED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
 7) TAMPER SWITCHES, CHAINS AND LOCKS ARE
 TO BE PROVIDED FOR BACKFLOW DEVICE.
 8) SUITABLE ROADS ARE TO BE PROVIDED
 DURING CONSTRUCTION FOR FIRE AND
 PARAMEDICAL ACCESS.
 9) FIRE DEPARTMENT CONNECTIONS FOR THE
 APARTMENT BUILDINGS ARE TO BE NO MORE
 THAN 150 FEET FROM NEARBY FIRE HYDRANTS.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910