Plan Review Notes
Plan Review Notes For Permit 01060486
Permit Number 01060486
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-06-14 00:00:00FAILED:
 1. INSUFFICIENT INFORMATION FOR CIVIL
 ENGINEERING REVIEW, PLEASE RESUBMIT
 WHEN CIVIL PLANS ARE COMPLETELY
 DEVELOPED.
 2. PLEASE SUBMIT SURVEYING PLANS
 3. PLEASE PROVIDE POLLUTION PREVENTION
 PLAN FOR ENTIRE SITE.POLLUTION
 PREVENTION MUST BE INSTALLED IN THE
 FIELD PRIOR TO ANY EARTH WORKS AND IT
 SHOULD INCLUDE PREVENTION OF TRACKING
 CONSTRUCTION DEBRIES AND DUST INTO THE
 PUBLIC R.O.W .THE PLAN SHOULD BE KEPT
 ON THE SITE DURING CONSTRUCTION.
 4. PLEASE PROVIDE THE STATUS OF APPROVAL
 FROM THE SFWMD IN REGARD TO THIS PROJECT
 5. ANY WORK WITHIN CITY PUBLIC R.O.W
 WILL REQUIRE A SEPARATE PERMIT THROUGH
 OFFICE OF CITY ENGINEER.659-8040
 6. ANY WORK WITHIN FDOT R.O.W WILL
 REQUIRE A SEPARATE PERMIT THROUGH FDOT
 DISTRICT OFFICE.
 7. ANY NEW CONNECTION TO CITY SERVICES
 WILL REQUIRE A SEPARATE PERMIT THROUGH
 PUBLIC UTILITIES ENGINEERING SERVICES
 DEPARTMENT. 659-8040
 8. PLEASE PROVIDE STORM WATER
 CALCULATIONS AND DETAILS FOR OUR REVIEW
 IF YOU HAVE NOT SUBMITTED TO JOSE DEL
 RIO, STORM WATER ENGINEER AT 1000 45TH
 STREET WPB, FL 33407.IF ALREADY SUB-
 MITTED, PLEASE PROVIDE THE STATUS OF
 APPROVAL.
 9. PLEASE PROVIDE PERVIOUS & IMPERVIOUS
 AREA CALCULATIONS.THE TOTAL AMOUNT
 MUST BE EQUAL TO 100% OF TOTAL SITE AREA
 IN ACRES OR S.F.
 10. PLEASE PROVIDE ADDRESS AND PROPERTY
 CONTROL NUMBER.
 11. PLEASE PROVIDE SIGNING AND MARKING
 FOR ENTIRE SITE.
 12. PLEASE PROVIDE LANDSCAPING PLANS.
 13. DUMPSTER ENCLOSURE MUST BE AT MIN.
 PER CITY STANDARD.SEE PREVIOUS REVIEW
 COMMENTS.
 14. PLEASE PROVIDE ADDITIONAL
 INFORMATION & DETAILS FOR EXISTING LIFT
 STATION.HAS THIS BEEN COORDINATED
 WITH PUBLIC UTILITIES ENGINEERING
 SEVICES DEPARTMENT FOR INSTALLATION,
 CONNECTION AND MAINTENANCE?
 15. NOTE 4 ON SHEET 7 OF 9A REFERS TO
 MANHOLES 20 AND 21
 A. THEY ARE NOT SHOWN ON SANITARY PLANS
 AND PROFILE SHEETS
 B. WHY ONLY THESE TWO WILL HAVE INSIDE &
 OUTSIDE COATINGS.
 16. CITY STANDARD AND DETAILS MAY BE
 OBTAINED FROM PUBLIC UTILITIES ENGINEER-
 ING SERVICES DEPARTMENT. 659-8040
 17. ALL BACKFLOW PREVENTERS SHALL BE
 COMPLETELY HIDDEN FROM VIEW WITH SHRUBS
 AND LANDSCAPING.
 18. SHEET 4 OF 11C IS MISSSING, PLEASE
 INCLUDE WITH RESUB.
 19. PLEASE REFER TO SHEET 3 & 5 OF 11C
 NOTES NO. 1, 11 AND VERIFY.
 20. PROVIDE TYP. SECTION FOR PERIMETER
 BERM AND FOR WATER MANAGEMENT TRACTS,
 SHOW SLOPE BOTTEM ELEVATIONS, ETC..
 21. PROVIDE DETAILS FOR PARKING STALLS
 H.C AND NONE-H.C
 22. PROVIDE DETAILS FOR PAVEMENTS,BASE
 AND SUB-BASE
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI