| 2001-06-14 00:00:00 | FAILED: |
| | 1. INSUFFICIENT INFORMATION FOR CIVIL |
| | ENGINEERING REVIEW, PLEASE RESUBMIT |
| | WHEN CIVIL PLANS ARE COMPLETELY |
| | DEVELOPED. |
| | 2. PLEASE SUBMIT SURVEYING PLANS |
| | 3. PLEASE PROVIDE POLLUTION PREVENTION |
| | PLAN FOR ENTIRE SITE.POLLUTION |
| | PREVENTION MUST BE INSTALLED IN THE |
| | FIELD PRIOR TO ANY EARTH WORKS AND IT |
| | SHOULD INCLUDE PREVENTION OF TRACKING |
| | CONSTRUCTION DEBRIES AND DUST INTO THE |
| | PUBLIC R.O.W .THE PLAN SHOULD BE KEPT |
| | ON THE SITE DURING CONSTRUCTION. |
| | 4. PLEASE PROVIDE THE STATUS OF APPROVAL |
| | FROM THE SFWMD IN REGARD TO THIS PROJECT |
| | 5. ANY WORK WITHIN CITY PUBLIC R.O.W |
| | WILL REQUIRE A SEPARATE PERMIT THROUGH |
| | OFFICE OF CITY ENGINEER.659-8040 |
| | 6. ANY WORK WITHIN FDOT R.O.W WILL |
| | REQUIRE A SEPARATE PERMIT THROUGH FDOT |
| | DISTRICT OFFICE. |
| | 7. ANY NEW CONNECTION TO CITY SERVICES |
| | WILL REQUIRE A SEPARATE PERMIT THROUGH |
| | PUBLIC UTILITIES ENGINEERING SERVICES |
| | DEPARTMENT. 659-8040 |
| | 8. PLEASE PROVIDE STORM WATER |
| | CALCULATIONS AND DETAILS FOR OUR REVIEW |
| | IF YOU HAVE NOT SUBMITTED TO JOSE DEL |
| | RIO, STORM WATER ENGINEER AT 1000 45TH |
| | STREET WPB, FL 33407.IF ALREADY SUB- |
| | MITTED, PLEASE PROVIDE THE STATUS OF |
| | APPROVAL. |
| | 9. PLEASE PROVIDE PERVIOUS & IMPERVIOUS |
| | AREA CALCULATIONS.THE TOTAL AMOUNT |
| | MUST BE EQUAL TO 100% OF TOTAL SITE AREA |
| | IN ACRES OR S.F. |
| | 10. PLEASE PROVIDE ADDRESS AND PROPERTY |
| | CONTROL NUMBER. |
| | 11. PLEASE PROVIDE SIGNING AND MARKING |
| | FOR ENTIRE SITE. |
| | 12. PLEASE PROVIDE LANDSCAPING PLANS. |
| | 13. DUMPSTER ENCLOSURE MUST BE AT MIN. |
| | PER CITY STANDARD.SEE PREVIOUS REVIEW |
| | COMMENTS. |
| | 14. PLEASE PROVIDE ADDITIONAL |
| | INFORMATION & DETAILS FOR EXISTING LIFT |
| | STATION.HAS THIS BEEN COORDINATED |
| | WITH PUBLIC UTILITIES ENGINEERING |
| | SEVICES DEPARTMENT FOR INSTALLATION, |
| | CONNECTION AND MAINTENANCE? |
| | 15. NOTE 4 ON SHEET 7 OF 9A REFERS TO |
| | MANHOLES 20 AND 21 |
| | A. THEY ARE NOT SHOWN ON SANITARY PLANS |
| | AND PROFILE SHEETS |
| | B. WHY ONLY THESE TWO WILL HAVE INSIDE & |
| | OUTSIDE COATINGS. |
| | 16. CITY STANDARD AND DETAILS MAY BE |
| | OBTAINED FROM PUBLIC UTILITIES ENGINEER- |
| | ING SERVICES DEPARTMENT. 659-8040 |
| | 17. ALL BACKFLOW PREVENTERS SHALL BE |
| | COMPLETELY HIDDEN FROM VIEW WITH SHRUBS |
| | AND LANDSCAPING. |
| | 18. SHEET 4 OF 11C IS MISSSING, PLEASE |
| | INCLUDE WITH RESUB. |
| | 19. PLEASE REFER TO SHEET 3 & 5 OF 11C |
| | NOTES NO. 1, 11 AND VERIFY. |
| | 20. PROVIDE TYP. SECTION FOR PERIMETER |
| | BERM AND FOR WATER MANAGEMENT TRACTS, |
| | SHOW SLOPE BOTTEM ELEVATIONS, ETC.. |
| | 21. PROVIDE DETAILS FOR PARKING STALLS |
| | H.C AND NONE-H.C |
| | 22. PROVIDE DETAILS FOR PAVEMENTS,BASE |
| | AND SUB-BASE |
| | IF ANY QUESTION PLEASE CONTACT 659-8096 |
| | EXT. 8492 MOHAMMAD R. AMINI |