Plan Review Notes
Plan Review Notes For Permit 01060467
Permit Number 01060467
Review Stop E
Sequence Number 1
Notes
Date Text
2001-06-24 00:00:00*******************UNSAT ************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE CLARIFY GROUNDING
 ELECTR0DE SYSTEM AT MAIN HOUSE SERVICE
 LOCATIONPLEASE NOTE THAT ZONING WILL
 HAVE TO OK TWO METERS.
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 3)NOTE: PLEASE NOTE THAT NO PANEL
 SCHEDULES OR LOAD CALCULATIONS WERE
 SUBMITTED.PER 215-5.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5)NOTE: PLEASE NOTE CLEARENCES PER
 110-26 FOR CLOSET SHOWING PANEL, A/C,
 WATER HEATER ETC ETC.
  
 6)NOTE: PLEASE NOTE THAT ELECTRICAL
 RISER IS SHOWN AS EXISTING UNDER PERMIT
 # 01021004. HOW IS THIS POSSIBLE WHEN TH
 AT PERMIT WAS FOR ANOTHER ADDRESS??
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved