| Date |
Text |
| 2001-06-24 00:00:00 | *******************UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2)NOTE: PLEASE CLARIFY GROUNDING |
| | ELECTR0DE SYSTEM AT MAIN HOUSE SERVICE |
| | LOCATIONPLEASE NOTE THAT ZONING WILL |
| | HAVE TO OK TWO METERS. |
| | |
| | 3) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 3)NOTE: PLEASE NOTE THAT NO PANEL |
| | SCHEDULES OR LOAD CALCULATIONS WERE |
| | SUBMITTED.PER 215-5. |
| | |
| | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 5)NOTE: PLEASE NOTE CLEARENCES PER |
| | 110-26 FOR CLOSET SHOWING PANEL, A/C, |
| | WATER HEATER ETC ETC. |
| | |
| | 6)NOTE: PLEASE NOTE THAT ELECTRICAL |
| | RISER IS SHOWN AS EXISTING UNDER PERMIT |
| | # 01021004. HOW IS THIS POSSIBLE WHEN TH |
| | AT PERMIT WAS FOR ANOTHER ADDRESS?? |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |