2001-09-17 00:00:00DENIED
 REFERENCE SPC-94 - FACBC-97
  
 1) PAGE A-6 WOMENS RESTROOM. FLOOR DRAIN
 NOT VENTED PROPERLY.
  
 2) PAGE A-7 WATER RISER DIAGRAM. WATER
 HAMMER ARRESTORS NOT LOCATED PROPERLY.
 PLEASE LOCATE HAMMER ARRESTORS PER MAN-
 UFACTURE INSTALLATION INSTRUCTIONS AND
 WH-PDI 201. SEE ATTACHED SHEET.
  
 REVIEW BY KEN STEVENS