| Notes |
| Date |
Text |
| 2001-09-24 00:00:00 | *****************PROVISO**************** | | | | | | | | | COMMENTS FROM 8-21-01 | | | | | | ALL RTU'S SHALL HAVE DUCT SMOKE | | | DETECTORS AS THE COMBINED AIR EXCEEDS | | | 2,000 CFM. | | | | | | | | | CONDENSATE SHALL TERMINATE TO STORM | | | DRAIN OR APPROVED DRYWELL.IT SHALL | | | NOT TERMINATE ON ROOF OR TO ANY AREA | | | WHERE IT COULD BE A NUISANCE. |
|