2001-09-24 00:00:00*****************PROVISO****************
  
  
 COMMENTS FROM 8-21-01
  
 ALL RTU'S SHALL HAVE DUCT SMOKE
 DETECTORS AS THE COMBINED AIR EXCEEDS
 2,000 CFM.
  
  
 CONDENSATE SHALL TERMINATE TO STORM
 DRAIN OR APPROVED DRYWELL.IT SHALL
 NOT TERMINATE ON ROOF OR TO ANY AREA
 WHERE IT COULD BE A NUISANCE.