Plan Review Notes
Plan Review Notes For Permit 01060376
Permit Number 01060376
Review Stop P
Sequence Number 2
Notes
Date Text
2001-08-22 00:00:00DENIED
  
 1) PAGE A-6, VENT NOT ALLOWED. NO DRY
 HORIZONTAL VENTS PER SPC-94 906.2.1
  
 2) WATER HEATER TO BE READILY ACCESSABLE
 PLEASE SHOW DETAILS.
  
 3) PAGE A-7, P&T RELIEF VALVE SHALL NOT
 BE TRAPPED PER SPC-94 507.8.4. THIS WAS
 NOT ADDRESSED FROM FIRST REVIEW.
  
 4) WATER HAMMER ARRESTORS TO BE INSTALL-
 ED PER MANUFACTURE'S INSTALLATION IN-
 STRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377