2001-09-17 00:00:00TRANSFERED NOTES FROM #01080151
  
 *************UNSAT******************
  
 1]NOTE: PLEASE NOTE SERVICE IS SHOWING
 TAPPED CONDUCTORS FROM METERCAN INTO
 GUTTER AND THEN TAPPING THE TAP???
 PLEASE NOTE THAT INDIVIDUAL RUNS FROM
 METERCAN TO EACH DISCONNECT IS
 PERMITTED. PLEASE SUBMIT.
  
 2]NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATINGS WERE
 SUBMITTED FOR PANELS BUT NOT FOR MAIN
 DISCONNECTS. PLEASE SUBMIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY
 QUESTIONS,PLEASE CALL.
  