| Plan Review Notes For Permit 01060376 |
| Permit Number |
01060376 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-09-17 00:00:00 | TRANSFERED NOTES FROM #01080151 | | | | | | *************UNSAT****************** | | | | | | 1]NOTE: PLEASE NOTE SERVICE IS SHOWING | | | TAPPED CONDUCTORS FROM METERCAN INTO | | | GUTTER AND THEN TAPPING THE TAP??? | | | PLEASE NOTE THAT INDIVIDUAL RUNS FROM | | | METERCAN TO EACH DISCONNECT IS | | | PERMITTED. PLEASE SUBMIT. | | | | | | 2]NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE THAT AIC RATINGS WERE | | | SUBMITTED FOR PANELS BUT NOT FOR MAIN | | | DISCONNECTS. PLEASE SUBMIT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY | | | QUESTIONS,PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT. 8372 |
|