| Plan Review Notes For Permit 01060376 |
| Permit Number |
01060376 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-23 00:00:00 | DENIED; | | | | | | 1.PAGE A-6, VENT FOR LAV 2, MEN'S ROOM, | | | IS REQUIRED TO BE CLOSER TO W/C 2 TO | | | BE VENTED PROPERLY. | | | | | | 2.WATER HEATER TO BE READLY ACCESIBLE. | | | PROVISIONS TO BE MADE SO NO TOOLS | | | ARE REQUIRED TO GET TO HEATER AND IT | | | CAN CHANGED . | | | | | | 3.BREAK SINK TO COMPLY WITH 97 SACBC SEC | | | 4.24.1 THRU 4.24.7. | | | | | | 4.DRINKING FOUNTAIN TO COMPLY WITH SACBC | | | 4.1.3(10) AND 4.15. PROVISIONS SHALL | | | BE MADE FOR PEOPLE WHO HAVE TROUBLE | | | BENDING OR STOOPING. | | | | | | 5.PAGE A-7 P.& T. RELIEF VALVE SHALL NOT | | | BE TRAPPED 94 SPC 507.8.4. | | | | | | 6.ENGINEERED WATER HAMMER ARRESTERS | | | SHALL BE INSTALLED PER SEC. 607.8.2 | | | AND 607.8.3. | | | | | | 7.PAGE A-8 PLUMBING NOTES (NOTE 20). | | | WATER DIAGRAM DOESNOT SHOW HOT WATER | | | TO THE LAV'S. DELETE NOTE 20 OR REVISE | | | WATER RISER DIAGRAM PG. A-7 AND WATER | | | DISTRIBUTION PLAN PG. A-6. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|