| Plan Review Notes For Permit 01060376 |
| Permit Number |
01060376 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-26 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | | ASHRAE 62-89. | | | | | | 2.AIR BALANCE SCHEDULE FOR COMPLIANCE | | | WITH 1997 SMC 501.2. | | | | | | 3.FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | REQUIRED FOR UNIT 5 TON AND LARGER | | | OR FOR UNITS SERVING AN AREA USED | | | FOR EGRESS. | | | | | | 4.FAN SHUT DOWN WITH NOTIFICATION TO | | | ALARM/STROBE IN NORMALLY OCCUPIED | | | AREAS AS PER NFPA 90A 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT.8388. |
|