| 2001-06-14 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE CLARIFY PANELS HAVING | | | BOTH BOXES MARKED FOR "MLO" AND "MCB" | | | ?? | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE THAT AIC RATINGS ARE SHOWN | | | FOR PANEL BUT NOT RATINGS FOR MAINS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|