| Notes |
| Date |
Text |
| 2001-07-04 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01060376 | | | 1572 PALM BEACH LAKES A 5-7 | | | CONTACT RICHARD WENSING ARCH | | | 684- 1988 | | | | | | PLAN REVIEW: TENANT BUILD OUT | | | | | | 1)- FLORIDA ACC.CODE 4.5 GROUND FLOORS | | | 4.5.3 CARPET & TILE ARE TO HAVE A STATIC | | | COEFFICIENT OF FRICTION OF 0.6 IS RECOM- | | | MENDED FOR ACCESSIBLE ROUTES AND 0.8 FOR | | | RAMPS. ( ADDAAG A-5) | | | | | | 2)- SBC 1204.2 THE WALLSAND FLOORS OF | | | ALL PUBLIC RESTROOMS SHALL BE LINED WITH | | | NONABSORBANT MATERIALS TO A HEIGTH OF | | | 4 FOOT ABOVE THE FLOOR. | | | | | | 3)- SBC 104.2.2 ADDITIONAL INFORMATION | | | REQUIRED: PLEASE INDICATE WHAT RAATING T | | | HE TENANT SEPERATION WALL HAS THAT SEPER | | | ATES THE ELECTRICAL ROOM & LOUNGE. | | | | | | 4)- MISSING IS THE MINIMUM INTERIOR FIN- | | | ISH CLASSIFICATION SCHEDULE TABLE 803.3. | | | GIVING THE FLAMESPREAAD & SMOKE DEVELOP- | | | MENT. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|