Plan Review Notes
Plan Review Notes For Permit 01060373
Permit Number 01060373
Review Stop M
Sequence Number 1
Notes
Date Text
2001-06-08 00:00:00*****************PROVISO****************
  
 ATTIC INSTALLATION OF AHU SHALL COMPLY
 WITH 1997 SMC 304.4.1, ACCESSIBLE BY AN
 OPENING & PASSAGEWAY LARGE AS THE
 LARGEST PIECE OF EQUIPMENT & IN NO CASE
 LESS THAN 22" X 36".
  
 AMMENDED 1997 SMC 304.4.2, SHALL HAVE AN
 ACCESSIBLE DISCONNECT SWITCH AND A
 110-20 VOLT A/C GROUNDING TYPE
 CONVENIENCE OUTLET & A LIGHT LOCATED ON
 SERVICE SIDE OF TH EQUIPMENT WITH A
 SWITCH LOCATED AT REQUIRED OPENING.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT.8388.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved