| Plan Review Notes For Permit 01060349 |
| Permit Number |
01060349 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-13 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE THAT AIC RATING WAS SUBMITTE | | | D FOR PANELS BUT NOT FOR MAIN. | | | | | | 2)NOTE: PLEASE CLARIFY OCP AND WIRE SIZE | | | OF #12 AWG FOR TRANSFORMER FEED FROM | | | PANEL "HA" TO "TB1". | | | | | | 3) NOTE: PLEASE SHOW ALL CONTINUOUS AT | | | 125%. (LIGHTING ETC) | | | PER 215-3 AND 230-42. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|