| Plan Review Notes For Permit 01060347 |
| Permit Number |
01060347 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-06-25 00:00:00 | 1) UNABLE TO LOCATE EMERGENCY LIGHT | | | FIXTURES FOR STORAGE AREA. EMERGENCY | | | LIGHT FIXTURES ARE REQUIRED. | | | 2) AFTER PERFORMING EXIT CALCULATIONS A | | | SINGLE EXIT IS NOT PERMITTED. TRAVEL | | | DISTANCE EXCEEDS 100 FEET WITH THE | | | FIRE SPRINKLER PROVISION BEING INCLUDED. | | | PLEASE PROVIDE LOCATION OF SECOND MEANS | | | OF EGRESS AND EXIT SIGN LOCATION. | | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR GENERATOR AND ANY FUEL STORAGE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|