| 2001-06-12 00:00:00 | ************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT UNDER F.S. AND |
| | F.A.C. ALL PLAN DONE BY AN ARCH/ENGINEER |
| | MUST BE SIGNED,DATED AND SEALED BY THE |
| | ARCH/ENG OF RECORD. 471.025 AND 481.221 |
| | |
| | 2)NOTE: PLEASE NOTE LOCATION OD GENERAT- |
| | -OR NOT SHOWN? |
| | |
| | 3)NOTE: PLEASE NOTE GROUPING OF DISCONNE |
| | CTS FOR MAIN AND GENERATOR.230-72 ALSO |
| | PLEASE NOTE 230-76 AND 230-79. |
| | |
| | 4) NOTE: PLEASE SHOW CALCULATIONS FOR |
| | TRACK LIGHTING PER 220-12B. |
| | |
| | 5) NOTE: PLEASE SHOW ALL CONTINUOUS AT |
| | 125%. (LIGHTING ETC) |
| | |
| | |
| | 6)NOTE: PLEASE CLARIFY 8 CIRCUITS SHOWN |
| | FOR BATTERY CHARGER?? |
| | |
| | 7)NOTE: PLEASE SHOW LOAD CALCULATIONS |
| | PER 220. SQ.FT ETC. |
| | |
| | 8)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL AND COLD WATER |
| | PER 250-50.GROUND ROD AND COLD WATER |
| | IF BLDG STEEL IS NOT AVAILABLE. |
| | |
| | 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 11)NOTE: PLEASE NOTE THAT OUTLET SPACING |
| | NEEDS TO MEET LOCAL CODE 210-50 FOR |
| | OUTSIDE WALL IN STORAGE AREA |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |