| Plan Review Notes For Permit 01060332 |
| Permit Number |
01060332 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-13 00:00:00 | ***************** UNSAT ************ | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE THAT AIC WAS SUBMITTED FOR | | | PANELS BUT NOT FOR MAIN. | | | | | | 2) PLEASE CLARIFY EQUIPMENT GROUNDING | | | METHOD BETWEEN FIRST MEANS OF | | | DISCONNECTAND PANEL(S). EQUIPMENT | | | GROUNDING CONDUCTORS ARE TO BE SIZED BY | | | ART 250-122. | | | | | | 3)NOTE: PLEASE NOTE THAT NO LOAD | | | CALCULATIONS WERE SUBMITTED ? PLEASE | | | SEE ART;220 | | | ALSO PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%.PER 215-3 AND 230-42 | | | | | | 4)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | | `#S ON PLANS AND CORRELATE WITH SUBMITT- | | | -ED PANEL SCHEDULES. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|