| 2001-06-14 00:00:00 | **************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT NO SIZE OF |
| | MAINDISCONNECT IS SHOWN. PLEASE SHOW |
| | |
| | 2) NOTE: PLEASE SHOW ALL OUTLETS |
| | SERVINGKITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECT--ED PER 210-8-A-6. |
| | |
| | 3)NOTE: PLEASE SHOW OTHER OUTLETS AS |
| | GFI/GFI PROTECTED PER 210-8. |
| | BATH/GARAGE. |
| | |
| | 4)NOTE: PLEASE NOTE THAT RISER DIAGRAM |
| | SHOWS MAIN DISCONNECT AND PLANS ONLY |
| | SHOW METER ON GARAGE . |
| | |
| | 5)NOTE: PLEASE NOTE THAT DISCONNECTS |
| | SHOWN FOR A/C COND UNIT DO NOT MEET |
| | 110-26. |
| | |
| | 6) PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.1 |
| | MECHANICAL CODE. |
| | |
| | 7)NOTE: MISSING OUTLET FOR HALLWAY PER |
| | 210-52H |
| | |
| | 8)NOTE: PLEASE NOTE MISSING OUTLET PER |
| | KITCHEN COUNTERTOP SPACING PER |
| | 210-52-C-1. |
| | |
| | 9)PLEASE CLARIFY EQUIPMENT GROUNDING |
| | METHOD BETWEEN FIRST MEANS OF |
| | DISCONNECTAND PANEL(S). EQUIPMENT |
| | GROUNDING |
| | CONDUCTORS ARE TO BE SIZED BY 250-122. |
| | |
| | 11)NOTE: PLEASE NOTE THAT THREE AIR |
| | HANDER UNITS ARE SHOWN WITH A LOAD OF |
| | 30KW |
| | AND ON LOAD CALCULATIONS, LOAD IS SHOWN |
| | AT 20KW? PLEASE CLARIFY. THIS IS FOR |
| | PANEL "B". |
| | |
| | 12)NOTE: PLEASE CLARIFY LOAD SHOWN FOR |
| | DRYER AT 8KW, 2P 50A AND #8. THIS DOES |
| | NOT SEEM TO BE COMMON SIZE. |
| | PLEASECLARIFY. |
| | |
| | 13)NOTE: PLEASE CLARIFY LOAD,OCP AND |
| | WIRE SIZE SHOW FOR OVEN? 20A,#12AWG AND |
| | 1.5KW.?IF THISIS A GAS OVEN PLEASE |
| | INDICATE ON PANEL SCHEDULE. |
| | |
| | 14)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | PLEASE NOTE MISSING SD`S IN A COUPLE OF |
| | AREAS. |
| | |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMAATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |