| 2001-06-08 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01060172 | | | 1214 ROEBUCK CT. | | | BAYS 5 & 6 | | | ABE SCHWARTZ A/C UNLIMITED | | | (561) 758-5593 | | | | | | 1)- SBC 104.2.2 ADDITIONAL INFORMATION | | | REQUIRED, SUBMIT THE PRE-ENGINEERED | | | SHOP DRAWINGS. | | | | | | 2)- SBC407.1.3.5. SPRAY BOOTHS WHERE | | | FLAMMABLES ARE USED SHALL BE PROTECTED | | | BY AN AUTOMATIC SPRINKLER SYSTEM. | | | | | | 3)- SPRAY BOOTHS SHALL BE CONSTRUCTED OF | | | STEEL NOT LESS THAN 1.2 MM THICK, | | | SECURELY & RIGIDLY SUPPORTED, OF | | | CONCRETE OR MASONARY OR OTHER APPROVED | | | NON COMBUSTIBLE MATERIAL. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|