Plan Review Notes
Plan Review Notes For Permit 01060035
Permit Number 01060035
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-06-22 00:00:001) GUARDHOUSE AND SECURITY FEATURES
 PLANNED ARE STILL NOT APPROVED. PREVIOUS
 PLAN REVIEW COMMENTS NOT ADDRESSED
 REFERENCE THE ENTRY SYSTEM AND
 APPURTENANCES.
 2) PLEASE BE ADVISED THAT CITY CODE
 SECTION 11-4 REQUIRES THAT NO
 OBJECTS BE PLACED WITHIN 18 FEET OF
 ANY FIRE HYDRANTS.
 3) ALL UNDERGROUND FIRE MAINS ARE TO BE
 LISTED FOR FIRE SERVICE AND COMPLY WITH
 NFPA 24.
 4) WHERE ARE THE BACKFLOW DEVICES
 LOCATED.
 5) PLEASE EXPLAIN PURPOSE OF ALL WATER
 VALVES SHOWN ON THE DRAWING. ARE SOME
 OF THESE VALVES REDUNDANT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910