| Plan Review Notes For Permit 01051593 |
| Permit Number |
01051593 |
|
| Review Stop |
P |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2002-05-16 00:00:00 | DENIED | | | REFERENCE: SPC-94 - SGC-97 - FACBC-97 | | | | | | 1) FROM PREVIOUS REVIEWS, SHTS P1/P2 | | | BAR AREA 3 COMPARTMENT SINK SHALL DRAIN | | | INDIRECTLY INTO A FLOOR SINK. FLOOR SINK | | | UNDER ICE BIN SHALL NOT HAVE FUNNEL AS | | | SHOWN ON RISER DIAGRAM. | | | 2) SHT P-1 FLOOR SINK TO BE UNDER FIX- | | | TURE AT ICE BINS. PLEASE SHOW PIPING ON | | | FLAT DRAWING FOR FLOOR SINK AND HAND | | | SINK AS REQUIETED IN LAST TWO REVIEWS. | | | 3RD REQUEST. | | | 3) SHTS P1/P2 RISER DIAGRAM AND FLOOR | | | PLAN STILL DO NOT MATCH. LAVS AND FLOOR | | | DRAIN SHALL COME OFF BLDG DRAIN ON RISER | | | DIAGRAM THE SAME AS ON THE FLOOR PLAN. | | | 3RD REQUEST. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|