| Plan Review Notes For Permit 01051593 |
| Permit Number |
01051593 |
|
| Review Stop |
P |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2002-04-24 00:00:00 | DENIED | | | REFERENCE: SPC-94 - SGC-97 - FACBC-97 | | | | | | 1) FROM PREVIOUS REVIEW, SHTS P-1/P-2 | | | BAR AREA 3 COMPARTMENT SINK STILL DRAINS | | | INTO THE FLOOR DRAIN. FLOOR SINK UNDER | | | ICE BIN IS A SAFE WASTE WHICH IS NOT | | | APPROVED. DOUBLE TRAPING IS NOT ALLOWED. | | | VENT FLOOR SINKS PROPERLY. | | | 2) SHT P-1 FLOOR SINK TO BE UNDER FIX- | | | TURE AT ICE BINS. PLEASE SHOW PIPING ON | | | FLAT DRAWING FOR FLOOR SINK AND HAND | | | SINK AS REQUESTED IN LAST REVIEW. 2ND | | | REQUEST. | | | 3) SHTS P-1/P-2 RISER DIAGRAM AND FLOOR | | | PLAN STILL DO NOT MATCH. LAVS AND FLOOR | | | DRAIN SHALL COME BLDG DRAIN ON RISER | | | DIAGRAM THE SAME AS ON THE FLOOR PLAN. | | | THIS COMMENT FROM LAST REVIEW. SEE RED | | | LINE MARKS ON PLANS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|