| Plan Review Notes For Permit 01051593 |
| Permit Number |
01051593 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2002-04-12 00:00:00 | ******************* UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT PANELS STILL | | | DO NOT CORRELATE!!!! | | | PLEASE NOTE THAT TOP OF PANELS NOW | | | SHOW 200A MCB BUT CONDUCTOR SIZES BELOW | | | PANEL SCHEDULES STILL SHOW WIRE FOR | | | 150A`S> | | | | | | 2)NOTE: PLEASE ALSO NOTE THAT RISER | | | DIAGRAM WAS NOT REVISED. PLEASE NOTE, | | | RISER DIAGRAM DOES NOT CORRELATE EITHER. | | | | | | 3)NOTE: PLEASE CORRECT AND PUT SETS OF | | | PLANS TOGETHER INTO TWO WORKING SETS. | | | PLEASE NOTE THAT THERE ARE REVISED SHEET | | | -S NOT PLACE IN SETS ETC. | | | | | | 4)NOTE: PLEASE NOTE THAT UNDER FS/ FAC | | | THESE PLANS HAVE BEEN DENIED FOR THE | | | SAME COMMENTS FOR THREE TIMES AND ARE | | | SUBJECT TO FOUR TIMES THE PLAN REVIEW | | | FEE!!!! PLEASE SEE SEC 553-80 FAC. | | | IF PLANS COME BACK IN AND ARE NOT | | | CORRECTED COMPLETELY, THERE WILL BE A | | | FOUR TIMES FEE AND A RED TAG WILL BE | | | WRITTEN IN VIOLATION OF TCO/CO. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|