Plan Review Notes
Plan Review Notes For Permit 01051593
Permit Number 01051593
Review Stop E
Sequence Number 6
Notes
Date Text
2002-04-12 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT PANELS STILL
 DO NOT CORRELATE!!!!
 PLEASE NOTE THAT TOP OF PANELS NOW
 SHOW 200A MCB BUT CONDUCTOR SIZES BELOW
 PANEL SCHEDULES STILL SHOW WIRE FOR
 150A`S>
  
 2)NOTE: PLEASE ALSO NOTE THAT RISER
 DIAGRAM WAS NOT REVISED. PLEASE NOTE,
 RISER DIAGRAM DOES NOT CORRELATE EITHER.
  
 3)NOTE: PLEASE CORRECT AND PUT SETS OF
 PLANS TOGETHER INTO TWO WORKING SETS.
 PLEASE NOTE THAT THERE ARE REVISED SHEET
 -S NOT PLACE IN SETS ETC.
  
 4)NOTE: PLEASE NOTE THAT UNDER FS/ FAC
 THESE PLANS HAVE BEEN DENIED FOR THE
 SAME COMMENTS FOR THREE TIMES AND ARE
 SUBJECT TO FOUR TIMES THE PLAN REVIEW
 FEE!!!! PLEASE SEE SEC 553-80 FAC.
 IF PLANS COME BACK IN AND ARE NOT
 CORRECTED COMPLETELY, THERE WILL BE A
 FOUR TIMES FEE AND A RED TAG WILL BE
 WRITTEN IN VIOLATION OF TCO/CO.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372