| Plan Review Notes For Permit 01051593 |
| Permit Number |
01051593 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2002-02-19 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 - SGC-97 | | | REVISION - REVIEW | | | 1) SHTS P-1/P-2 W/C IN WOMENS RESTROOM | | | THAT WAS MOVED NOT SHOWN ON RISER DIAG. | | | 2) SHTS P-1/P-2 BAR AREA. 3 COMP SINK TO | | | AND ICE MACKINE TO DRAIN TO FLOOR SINK | | | UNDER FIXTURE. FLOOR PLAN SHOWS A FLOOR | | | DRAIN. A FLOOR SINK SHALL BE ADDED AND | | | SHALL BE LOCATED UNDER FIXTURE FOR IN- | | | DIRECT WASTE TO DRAIN INTO. | | | 3) SHT P-1 FLOOR SINK TO BE UNDER FIX- | | | TURE AT ICE BINS. PLEASE SHOW PIPING ON | | | FLAT DRAWING FOR FLOOR SINK AND HAND | | | SINK. | | | 4) SHTS P-1/P-2 RISER DIAGRAM DOES NOT | | | MATCH FLOOR PLAN DRAWING. LAVS AND FLOOR | | | DRAIN SHALL COME OFF BLDG DRAIN ON RISER | | | DIAGRAM THE SAME AS ON FLOOR PLAN. | | | 5) PLEASE CLOUD ALL CHANGES FOR EACH RE- | | | VISION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|