Plan Review Notes
Plan Review Notes For Permit 01051593
Permit Number 01051593
Review Stop P
Sequence Number 5
Notes
Date Text
2002-02-19 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SGC-97
 REVISION - REVIEW
 1) SHTS P-1/P-2 W/C IN WOMENS RESTROOM
 THAT WAS MOVED NOT SHOWN ON RISER DIAG.
 2) SHTS P-1/P-2 BAR AREA. 3 COMP SINK TO
 AND ICE MACKINE TO DRAIN TO FLOOR SINK
 UNDER FIXTURE. FLOOR PLAN SHOWS A FLOOR
 DRAIN. A FLOOR SINK SHALL BE ADDED AND
 SHALL BE LOCATED UNDER FIXTURE FOR IN-
 DIRECT WASTE TO DRAIN INTO.
 3) SHT P-1 FLOOR SINK TO BE UNDER FIX-
 TURE AT ICE BINS. PLEASE SHOW PIPING ON
 FLAT DRAWING FOR FLOOR SINK AND HAND
 SINK.
 4) SHTS P-1/P-2 RISER DIAGRAM DOES NOT
 MATCH FLOOR PLAN DRAWING. LAVS AND FLOOR
 DRAIN SHALL COME OFF BLDG DRAIN ON RISER
 DIAGRAM THE SAME AS ON FLOOR PLAN.
 5) PLEASE CLOUD ALL CHANGES FOR EACH RE-
 VISION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377