| Plan Review Notes For Permit 01051593 |
| Permit Number |
01051593 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2002-02-19 00:00:00 | ****************** UNSAT ************ | | | | | | PLEASE NOTE THAT THESE PLANS ARE FOR | | | FINAL/CO.PLEASE NOTE THAT PLANS NEED TO | | | CORRELATE COMPLETELY WITH JOBSITE. | | | | | | 1)NOTE: PLEASE NOTE/VERIFY THAT ALL | | | PANELS ARE 200AMP. PLEASE NOTE THAT PER | | | FEILD INSPECTIONPANELS 'C,D,E,F' ARE | | | ALL 200A MCB. | | | | | | 2)NOTE: PLEASE ALSO NOTE THAT SOME | | | PANELS ARE SHOWN AS RECESSED? PLEASE | | | NOTE THAT 'A,B,C,D,E,F' ARE ALL SURFACE | | | MOUNTED. | | | | | | PLEASE VERFIY AND MAKE THE CHANGES AS | | | NEEDED.PLEASE SUBMIT FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|