| Plan Review Notes For Permit 01051593 |
| Permit Number |
01051593 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2002-01-07 00:00:00 | REVISIONS #1, #2 DEC.10/01 | | | DENIED!!!! | | | 1)- HANDICAPPED STALLS, FL ACC CODE | | | 4.17.3 FIG. 30 "E" REQUIRES THE WATER | | | CLOSET SHALL BE LOCATED IN THE CORNER | | | DIAGONAL TO THE DOOR!!!!!AS PER THE | | | FIRST SET OF REVISIONS!!!!! | | | | | | 2)- FRONT ENTRY,(FOYER) SBC 1019.2.3 | | | REMOVAL OF PERMANENT BARRIER SEPERATING | | | THE WAITING AREA FROM THE REQUIRED CLEAR | | | WIDTH FOR EXITS. | | | | | | 3)- DELETION OF 2 HR.HORIZONTAL PASSAGE | | | WAY. BEHIND STORAGE UNIT # 1!!!!!! | | | | | | 4)- BAR AREA # 2, SHOW EGRESS PATH , | | | CLEAR FLOOR AREA. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X8412 |
|