Plan Review Notes
Plan Review Notes For Permit 01051593
Permit Number 01051593
Review Stop E
Sequence Number 4
Notes
Date Text
2001-12-12 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE, THAT AS PER CONVER-
 -SATION WITH THE ELECTRICAL INSPECTOR,
 PLEASE PROVIDE LAYOUT OF THE ELECTRICAL
 ROOM ON PLANS AS IT IS IN THE FIELD.
  
 2)NOTE: PLEASE NOTE, LOAD SHOWN FOR
 PANEL "E IS DIFFERENT FROM LOAD CALCULA-
 -TION FOR ALL PANELS.
  
 3)NOTE: PLEASE PROVIDE LOAD ON LINE SIDE
 OF TRANSFORMER.
  
 4)NOTE: PLEASE CLARFIY HOW MANY CONDUITS
 ARE COMING FROM LOAD SIDE OF TRANSFORMER
 TO DISC AND FROM DISC TO 12"X12"X9'
 GUTTER. PER ELECTRICAL INSPECTOR, THE
 FIELD INSTALLATION HAS ONLY ONE 2 1/2"
 CONDUIT INSTALLED WITH 4-3/0`S AND
 SOME CONFUSION OF THE ELECTRICAL CONTRAC
 TOR.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND PERHAPS MEET WITH THE ELEC
 CONTRACTOR AND/OR ELECTRICAL INSPECTOR
 ON THE JOB.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372