| Plan Review Notes For Permit 01051593 |
| Permit Number |
01051593 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-12-12 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE, THAT AS PER CONVER- | | | -SATION WITH THE ELECTRICAL INSPECTOR, | | | PLEASE PROVIDE LAYOUT OF THE ELECTRICAL | | | ROOM ON PLANS AS IT IS IN THE FIELD. | | | | | | 2)NOTE: PLEASE NOTE, LOAD SHOWN FOR | | | PANEL "E IS DIFFERENT FROM LOAD CALCULA- | | | -TION FOR ALL PANELS. | | | | | | 3)NOTE: PLEASE PROVIDE LOAD ON LINE SIDE | | | OF TRANSFORMER. | | | | | | 4)NOTE: PLEASE CLARFIY HOW MANY CONDUITS | | | ARE COMING FROM LOAD SIDE OF TRANSFORMER | | | TO DISC AND FROM DISC TO 12"X12"X9' | | | GUTTER. PER ELECTRICAL INSPECTOR, THE | | | FIELD INSTALLATION HAS ONLY ONE 2 1/2" | | | CONDUIT INSTALLED WITH 4-3/0`S AND | | | SOME CONFUSION OF THE ELECTRICAL CONTRAC | | | TOR. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND PERHAPS MEET WITH THE ELEC | | | CONTRACTOR AND/OR ELECTRICAL INSPECTOR | | | ON THE JOB. | | | IF THERE ARE ANY QUESTIONS,PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|