Plan Review Notes
Plan Review Notes For Permit 01051593
Permit Number 01051593
Review Stop M
Sequence Number 2
Notes
Date Text
2001-07-09 00:00:00*******************DENIED***************
  
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION AND WALK-IN COOLERS.
 PLEASE PROVIDE PLANS WITH MANUFACTURER
 SUBMITTAL DATA WITH PERMIT APPLICATIONS.
  
 PROVIDE LOCATION OF THE FLUE PIPE FOR
 GAS WATER HEATER.
  
 SUPPLY DUCT TO STORAGE ROOM APPEARS TO
 PENETRATE A RATED WALL, FIRE DAMPER IS
 REQUIRED.PLEASE PROVIDE MANUFACTURER
 DETAILS FOR COMPLIANCE WITH 1997 SMC
 610.1.2.LOCATIONS OF FIRE DAMPERS
 NEEDTO BE INDICATED ON PLAN.
  
 NOTE:NO COMBUSTIBLES ABOVE THE CEILING
 IN THE RETURN AIR PLENUM.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS 659-8096 EXT. 8338.