Text |
| 2001-07-22 00:00:00 | ****************UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SHOW GROUNDING REQUIRED |
| | FOR TRANSFORMER. TO WHERE? |
| | |
| | 2)NOTE: PLEASE NOTE THAT IN THE "96" NEC |
| | IT NOTES UNDER 450-21B TRANSFORMERS TO |
| | BE 80C OR HIGHER AND "99" NEC CLASS 155 |
| | OR HIGHER. PLANS SHOW 80F? |
| | WE ARE UNDER THE "99" NEC AND THEREFORE |
| | NOTE FOR TRANSFORMER NEEDS TO CLASS 155. |
| | |
| | |
| | 3)NOTE: PLEASE SUBMIT CLARIFICATION ON |
| | 400A DISCONNECT FROM EXISTING ELEC ROOM. |
| | IS IT FUSED AT 250A`S?? PLANS SHOW A |
| | 400A DISC FEEDING AT 250A DISC W/ 250A |
| | FUSES? PLEASE CLARIFY. |
| | |
| | 4)NOTE: PLEASE NOTE THAT NO AIC RATINGS |
| | WERE SUBMITTED FOR LINE AND LOAD DISC`S |
| | FOR TRANSFORMER. |
| | |
| | 5)NOTE: PLEASE NOTE THAT ALL PANEL |
| | SCHEDULES SHOW PANELS BEING RECESSED, |
| | AND PLAN ON E-1 SHOWS PANELS AS SURFACE |
| | MOUNTED? PLEASE CLARIFY. |
| | PLEASE NOTE THAT AS PER ELECTRICAL ROOM |
| | LAYOUT ON E-1 AND SCALE SHOWN BELOW |
| | AT 1/2" TO 1'. THE CLEARENCES DON'T SHOW |
| | AS BEING ENOUGH. ALSO PLEASE NOTE THAT |
| | DURING CONTRUCTION WE HAVE RUN INTO |
| | MORE OFTEN THAN NOT THAT ELECTRICAL |
| | ROOMS ARE NOT BUILT LARGE ENOUGH. |
| | MANY WALL HAVE BEEN MOVED IN THE PAST TO |
| | MEET CODE. PLEASE VERIFY THAT ALL |
| | CLEARENCES MEET OR EXCEED REQ`D SPACES |
| | FOR 110-26 AND 450-21. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |