Plan Review Notes
Plan Review Notes For Permit 01051593
Permit Number 01051593
Review Stop E
Sequence Number 2
Notes
Date Text
2001-07-22 00:00:00****************UNSAT ***************
  
 1)NOTE: PLEASE SHOW GROUNDING REQUIRED
 FOR TRANSFORMER. TO WHERE?
  
 2)NOTE: PLEASE NOTE THAT IN THE "96" NEC
 IT NOTES UNDER 450-21B TRANSFORMERS TO
 BE 80C OR HIGHER AND "99" NEC CLASS 155
 OR HIGHER. PLANS SHOW 80F?
 WE ARE UNDER THE "99" NEC AND THEREFORE
 NOTE FOR TRANSFORMER NEEDS TO CLASS 155.
  
  
 3)NOTE: PLEASE SUBMIT CLARIFICATION ON
 400A DISCONNECT FROM EXISTING ELEC ROOM.
 IS IT FUSED AT 250A`S?? PLANS SHOW A
 400A DISC FEEDING AT 250A DISC W/ 250A
 FUSES? PLEASE CLARIFY.
  
 4)NOTE: PLEASE NOTE THAT NO AIC RATINGS
 WERE SUBMITTED FOR LINE AND LOAD DISC`S
 FOR TRANSFORMER.
  
 5)NOTE: PLEASE NOTE THAT ALL PANEL
 SCHEDULES SHOW PANELS BEING RECESSED,
 AND PLAN ON E-1 SHOWS PANELS AS SURFACE
 MOUNTED? PLEASE CLARIFY.
 PLEASE NOTE THAT AS PER ELECTRICAL ROOM
 LAYOUT ON E-1 AND SCALE SHOWN BELOW
 AT 1/2" TO 1'. THE CLEARENCES DON'T SHOW
 AS BEING ENOUGH. ALSO PLEASE NOTE THAT
 DURING CONTRUCTION WE HAVE RUN INTO
 MORE OFTEN THAN NOT THAT ELECTRICAL
 ROOMS ARE NOT BUILT LARGE ENOUGH.
 MANY WALL HAVE BEEN MOVED IN THE PAST TO
 MEET CODE. PLEASE VERIFY THAT ALL
 CLEARENCES MEET OR EXCEED REQ`D SPACES
 FOR 110-26 AND 450-21.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  