| 2001-07-30 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01051593 |
| | 550 S ROSEMARY AVE # 250 |
| | ACCESS CONSTRUCTION TEAM |
| | (813) 274-7770 |
| | |
| | SBC= STANDARD BUILDING CODE |
| | SBC*= STANDARD BUILDING CODE AMENDMENTS |
| | FL ACC= 1997 FLORIDA ACCESSIBILITY CODE |
| | |
| | 1)- SHOWROOM LEVELS 2.0, 2.1, 2.2 & |
| | LEVEL 3.0 ARE IN AN ASSEMBLY OCCUPANCY |
| | OCCUPANCY. SBC 1019.8: IN BUILDINGS OF |
| | GROUP A OCCUPANCY, FLIGHTS OF LESS THAN |
| | (3) THREE RISERS SHALL NOT BE USED IN |
| | INTERIOIR OR EXTERIOR STAIRWAYS, EXIT |
| | PASSAGE WAYS, AISLES, AT ENTRANCES OR |
| | ELSEWHERE IN CONNECTION WITH REQUIRED |
| | EXITS. TO OVERCOME LESSER DIFFERENCES |
| | IN LEVEL, RAMPS MAY BE USED. |
| | |
| | 2)- WHERE THERE IS A ELEVATION CHANGE, |
| | LEVEL 2.0, 2.1, 2.2 & 3.0 VERTICAL |
| | ACCESSIBILITY MUST BE PROVIDED. FL |
| | ACCESSIBILITY CODE 4.1.3 THE STAGE ALSO |
| | MUST MEET THE VERTICAL ACCESSIBILITY |
| | REQUIREMENTS BUT DEPENDING ON THE HEIGTH |
| | OF THE STAGE HANDRAIL REQUIUREMENTS |
| | FL ACC. 4.8.2. |
| | |
| | 3)- FL ACCESSIBILITY CODE: 4.8.3 CLEAR |
| | WIDTH, RAMPS THAT ARE USED AS A MEANS OF |
| | EGRESS SHALL NOT BE LESS THAN 44" WIDE. |
| | |
| | 4)- FL ACC CODE RAMPS 4.8.4 (LEVEL 2.2) |
| | ALL LANDINGS ON RAMPS SHALL BE NOT LESS |
| | THAN 60" CLEAR, AND THE BOTTOM OF EACH |
| | RAMP SHALL HAVE NOT LESS THAN 72" OF |
| | STRAIGHT AND LEVEL SURFACE. |
| | |
| | 5)_ FL ACC CODE 4.8.5 HANDRAILS: IF A |
| | RAMP HAS A RISE GREATER THAN 6" OR A |
| | HORIZONTAL PROJECTION GREATER THAN 72", |
| | THEN IT SHALL HAVE HANDRAILS ON BOTH |
| | SIDES. |
| | |
| | 6)- SHEET E.5 INDICATES THAT THE 225KVA |
| | TRANSFORMER IS IN THE ELECTRIC ROOM, |
| | WHAT IS SUPPORTING THE TRANSFORMER? |
| | |
| | 7)- REVISE THE LIFE SAFETY PLAN TO |
| | INCLUDE LEVEL 2.2 64 PEOPLE FOR FIXED |
| | SEATING AND 64' OF BAR @ 2' PER PERSON |
| | OR ANOTHER 32 PEOPLE. |
| | |
| | 8)- THE CORRIDOR BEHIND THE KITCHEN WILL |
| | NEED TO BE AN EXIT CORRIDOR, SINCE THIS |
| | IS AN ASSEMBLY OCCUPANCY THE TABLE |
| | 705.1.2 OF THE SBC REQUIRES A 2 HR. |
| | RATING ON WALLS CEILING AND FLOOR. ALL |
| | OPENINGS WILL REQUIRE AN 1 1/2 HR. OPEN- |
| | ING PROTECTION, AND THE CORRIDOR HAS TO |
| | EXTEND TO THE EXTERIOR OF THE BUILDING. |
| | |
| | 9)- PROVIDE PRODUCT APPROVAL ON ALL |
| | EXTERIOR GLAZING, TO INDICATE CONFORMITY |
| | WITH IMPACT REQUIREMENTS FOR HURRICANE |
| | PROTECTION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 X 8412 |