2001-07-30 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01051593
 550 S ROSEMARY AVE # 250
 ACCESS CONSTRUCTION TEAM
 (813) 274-7770
  
 SBC= STANDARD BUILDING CODE
 SBC*= STANDARD BUILDING CODE AMENDMENTS
 FL ACC= 1997 FLORIDA ACCESSIBILITY CODE
  
 1)- SHOWROOM LEVELS 2.0, 2.1, 2.2 &
 LEVEL 3.0 ARE IN AN ASSEMBLY OCCUPANCY
 OCCUPANCY. SBC 1019.8: IN BUILDINGS OF
 GROUP A OCCUPANCY, FLIGHTS OF LESS THAN
 (3) THREE RISERS SHALL NOT BE USED IN
 INTERIOIR OR EXTERIOR STAIRWAYS, EXIT
 PASSAGE WAYS, AISLES, AT ENTRANCES OR
 ELSEWHERE IN CONNECTION WITH REQUIRED
 EXITS. TO OVERCOME LESSER DIFFERENCES
 IN LEVEL, RAMPS MAY BE USED.
  
 2)- WHERE THERE IS A ELEVATION CHANGE,
 LEVEL 2.0, 2.1, 2.2 & 3.0 VERTICAL
 ACCESSIBILITY MUST BE PROVIDED. FL
 ACCESSIBILITY CODE 4.1.3 THE STAGE ALSO
 MUST MEET THE VERTICAL ACCESSIBILITY
 REQUIREMENTS BUT DEPENDING ON THE HEIGTH
 OF THE STAGE HANDRAIL REQUIUREMENTS
 FL ACC. 4.8.2.
  
 3)- FL ACCESSIBILITY CODE: 4.8.3 CLEAR
 WIDTH, RAMPS THAT ARE USED AS A MEANS OF
 EGRESS SHALL NOT BE LESS THAN 44" WIDE.
  
 4)- FL ACC CODE RAMPS 4.8.4 (LEVEL 2.2)
 ALL LANDINGS ON RAMPS SHALL BE NOT LESS
 THAN 60" CLEAR, AND THE BOTTOM OF EACH
 RAMP SHALL HAVE NOT LESS THAN 72" OF
 STRAIGHT AND LEVEL SURFACE.
  
 5)_ FL ACC CODE 4.8.5 HANDRAILS: IF A
 RAMP HAS A RISE GREATER THAN 6" OR A
 HORIZONTAL PROJECTION GREATER THAN 72",
 THEN IT SHALL HAVE HANDRAILS ON BOTH
 SIDES.
  
 6)- SHEET E.5 INDICATES THAT THE 225KVA
 TRANSFORMER IS IN THE ELECTRIC ROOM,
 WHAT IS SUPPORTING THE TRANSFORMER?
  
 7)- REVISE THE LIFE SAFETY PLAN TO
 INCLUDE LEVEL 2.2 64 PEOPLE FOR FIXED
 SEATING AND 64' OF BAR @ 2' PER PERSON
 OR ANOTHER 32 PEOPLE.
  
 8)- THE CORRIDOR BEHIND THE KITCHEN WILL
 NEED TO BE AN EXIT CORRIDOR, SINCE THIS
 IS AN ASSEMBLY OCCUPANCY THE TABLE
 705.1.2 OF THE SBC REQUIRES A 2 HR.
 RATING ON WALLS CEILING AND FLOOR. ALL
 OPENINGS WILL REQUIRE AN 1 1/2 HR. OPEN-
 ING PROTECTION, AND THE CORRIDOR HAS TO
 EXTEND TO THE EXTERIOR OF THE BUILDING.
  
 9)- PROVIDE PRODUCT APPROVAL ON ALL
 EXTERIOR GLAZING, TO INDICATE CONFORMITY
 WITH IMPACT REQUIREMENTS FOR HURRICANE
 PROTECTION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412