| 2001-06-03 00:00:00 | PLUMBING PLAN REVIEW"DENIED" |
| | (1) DEPT OF HOTEL BUSINESS REGULATION |
| | PLAN REVIEW REQUIRED BEFORE PLUMBING |
| | PLAN REVIEW, CONTACT 954-958-5520. |
| | (2)SHT A1.0,OCCUPANCY AT 356 PERSONS, NO |
| | SEATING SHOWN FOR LOUNGE,DINING RM'S 1,2 |
| | ALSO NUMBER OF EMPLOYEES, THIS MAY |
| | CHANGE THE NUMBER OF FACILITIES REQUIRED |
| | COMPLY W/FACBC 4.1.3(19)(A),AREAS OF |
| | ASSEMBLY WITH FIXED SEATING,SPC TAB 407. |
| | (3) SHT A1.2 WOMENS REST RM COMPLY WITH |
| | FACBC 97 FOR THE FOLLOWING.SEC 4.22.4 |
| | WHEN 6 OR MORE STALLS ARE PROVIDE, ONE |
| | MUST BE ACCESSIBLE,GRAB BARS,DOOR SWING. |
| | W/C FLUSH HANDLE,MOUNTING SIDE SEC4.16.5 |
| | W/C GRAB BARS BACK SIDE 36" SEC4.17.6 |
| | DOORS SHALL NOT SWING INTO CLEAR FLOOR |
| | SPACE OF ANY FIXTURE SEC 4.23.2 |
| | ONE OF THE LAVATORIES OUTSIDE OF THE H/C |
| | STALL IN THE MEN'S ,WOMEN'S REST RM |
| | SHALL COMPLY W/SEC 4.23.6 & 4.19 |
| | (4) SHT P-1 MEN'S REST RM,H/C STALL |
| | FLR DRAIN REQ,SPC 94 SEC 409.4 |
| | (5) SHT P-1 DISH WASHER,TO SANITARY |
| | SEWER. LOCAL ORD #2838-96 WPB RSTP. |
| | (6) SHT P-2 ITEMS #6,10,29 TO FLR SINKS |
| | SPC 94, SEC 921.4,HORZONTAL WASTE VENT. |
| | (7) SHT P-2ITEMS #4,27,30 NO RUNNING |
| | TRAPS,SPC 94 SEC 1001.8.3 INDIVIDUAL |
| | TRAPS FOR EACH COMPARTMENT. |
| | (8) SHT P-2,SEE ATTACHED GAS PERMIT |
| | APPLICATION REQUIRMENTS,SGC97, SEC 104.3 |
| | ADDRESS EACH OF NINE ITEMS. |
| | (9) SHT P-1,PLBG NOTE 2.1 & SHT P-3, |
| | AIR CHAMBERS, SPC 94, SEC 607.8.3 TO BE |
| | ACCESSIBLE & RECHARGEABLE. |
| | END OF COMMENTSPAUL SCHMITZ |
| | QUESTIONS561-659-8096X8233 |