| Date |
Text |
| 2001-06-01 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS INCLUDED |
| | WITH PLANS. PLEASE PROVIDE FIRE |
| | SPRINKLER DRAWINGS. |
| | 2) PROVISIONS ARE TO BE MADE FOR AT |
| | LEAST TWO HANDICAPPED PERSONS. |
| | 3) NO INTERIOR FINISH CLASSIFICATION |
| | INFORMATION PROVIDED WITH PLANS. |
| | 4) PANIC HARDWARE REQUIRED ON ALL |
| | EXIT DOORS SINCE OCCUPANCY IS EXPECTED |
| | TO BE OVER 100 PERSONS. FIRE EXIT PANIC |
| | HARDWARE REQUIRED FOR ALL FIRE DOORS. |
| | 5) NO SEATING SHOWN FOR LOUNGE OR DINING |
| | ROOM NUMBER 2. |
| | 6) PLEASE EXPLAIN EXITING RATIONALE TO |
| | THIS OFFICE. THE STAIRWELL EXIT DOOR |
| | NEAR OFFICE NUMBER 2 IS SHARED WITH |
| | ANOTHER ASSEMBLY OCCUPANCY. ONLY HALF |
| | CREDIT WILL BE GIVEN FOR THIS STAIR |
| | SINCE IT IS SHARED. THE FOUR SWINGING |
| | DOORS FROM SHOWROOM LEVEL ONE OPEN |
| | INTO LOUNGE WHERE ONLY TWO SWINGING |
| | DOORS ARE PROVIDED TO ENTER THE FOYER |
| | AREA. PLEASE INDICATE ON PLANS WHERE THE |
| | MAIN EXIT IS PROVIDED TO ACCOMODATE |
| | AT LEAST FIFTY PERCENT OF THE TOTAL |
| | OCCPANT LOAD. |
| | 7) NO BAR STOOLS SHOWN FOR BAR NUMBER |
| | ONE. |
| | 8) PLEASE PROVIDE A LIFE SAFETY PLAN TO |
| | THIS OFFICE WITH THE NEXT SUBMITTAL. |
| | 9) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR THE HOOD,DUCT AND EXTINGUISHING |
| | SYSTEMS. |
| | 10) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR THE FIRE ALARM SYSTEM REMODEL. |
| | 11) PLEASE INDICATE CONSTRUCTION TYPE |
| | FOR STAGE. |
| | 12) PLEASE INDICATE NUMBER OF STAFF |
| | PERSONS SO THEY CAN BE INCLUDED IN |
| | OCCUPANT LOAD |
| | 13) NO EXIT SIGNS SHOWN NEAR DOUBLE |
| | DOORS FROM SHOWROOM NUMBER ONE. |
| | 14) ANY CHANGES IN ELEVATION LESS THAN |
| | TWENTY ONE INCHES SHALL BE BY RAMPS. |
| | 15) PLEASE INDICATE IF THERE ARE ANY |
| | WAITING SPACES IN THE SPACE. |
| | 16) PLEASE EXPLAIN US OF NEW PATIO. |
| | 17) PLEASE IDENTIFY IF A COLUMN IS |
| | PRESENT NEAR EXIT DOOR NEAR BAR NUMBER |
| | ONE. |
| | |
| | CAPTAIN MIKE CARSILLO |
| | 659-8096,EXT.8497 |
| | 835-2910 |