Plan Review Notes
Plan Review Notes For Permit 01051593
Permit Number 01051593
Review Stop E
Sequence Number 1
Notes
Date Text
2001-06-12 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT OUTLET SPACING
 NEEDS TO MEET LOCAL CODE PER ART 210-50
 STORAGE AREAS/ EVERY 20' OF
 UNENCUMBEREDWALL SPACE AND OFFICE AREAS
 EVERY 12"
 THE AREAS WHERE PATRONS/PUBLIC LOOKS TO
 BE AREA IN QUESTION. PLEASE NOTE EVERY
 20' AND PLACE BRANCH CIRCUIT #`S ON
 PLANS THAT CORRELATE WITH PANEL SCHEDULE
  
  
 2)NOTE: PLEASE NOTE THAT PANEL"C" PANEL
 SCHEDULE SHOWS MLO AND RISER SHOWS MCB.
 PLEASE CALRIFY.
  
 3)NOTE: PLEASE NOTE THAT GROUNDING FOR
 TRANSFORMER NEEDS TO BE CLARIFIED. PER
 450-5 AND 450-10
  
 4)NOTE: PLEASE NOTE 450-13 FOR ACESS.
 PLEASE SHOW TRANSFORMER LOCATION ON
 PLANS.PLANS NOTE TRANSFORMER HANGING
 FROM CEILING BUT NOT WHERE.
 PLEASE ALSO NOTE THAT ART 450-21B FOR
 TRANSFORMERS OVER 112.5 KVA NEED TO BE
 INSTALLED IN A TRANSFORMER VAULT.
  
 5)NOTE: PLEASE NOTE WIRE SIZE SHOWN FOR
 PANEL "B" ON E-5AS 4-1/0`S FOR 200A.
 PLEASE CORRECT.
  
 6)NOTE: PLEASE NOTE ACCESSABLITY FOR
 ALL DISCONNECTS AND CLEARENCES PER
 11-26. PLEASE CLARIFICATION FOR DISCO-
 -NNECTS FOR TRANSFORMER// LINE AND LOAD.
  
 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATING WAS
 SUBMITTED FOR PANELS, BUT NOT FOR MAIN
 OR DISC.
  
 8)NOTE: PLEASE FEILD VERIFY SIZE OF
 EXSITING CONDUCTORS SHOWN FOR MAIN.
 PLEASE CLARIFY FOR ART 240-3B
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372