| 2001-06-18 00:00:00 | BUILDING PLAN REVIEW COMMENTS 6/18. |
| | 1. PAY IMPACT FEES, PALM BEACH COUNTY TO |
| | STAMP PLANS. |
| | 2. SHEET A1.0, PROVIDE LIFE SAFETY PALN |
| | FOR LOUNGE, DINING 1 AND 2, BAR AND |
| | EXTERIOR SEATING AREAS. INDICATE EXIT |
| | ILES FOR ALL AREAS. |
| | 3. INDICATE HANDICAPPED ACCESS FOR |
| | LEVELS 2 AND 2.1. RAMPS REQUIRED SEE |
| | SBC 1019.8 AND FLORIDA ACCESSABILITY |
| | CODE 4.1.3. |
| | |
| | 4. SHEETS A1.1, A1.2 AND A2.1 WHERE |
| | REVIWED WITHOUT APPROVAL OF DESIGNER OF |
| | RECORD INITIALS AND DATE. |
| | 5. SHEET E.5 PROVIDE ENGINEERING ON 225 |
| | KVA TRASNSFORMER SUSPENDED FROM BOTTOM |
| | COURD OF ROOF TRUSSES. |
| | 5. SHEET AC.2 ENGINNER TO PROVIDE DESIGN |
| | FOR FAN COIL SUPPORT ATTACHED TO BOTTOM |
| | COURD OF ROOF TRUSSES. |
| | 6. PROVIDE INFORMATION ON FIRE STOPPING |
| | SYSTEMS TO BE USED ON ALL FIRE RATED |
| | HORZONTIALL AND VERTICAL PENATRATIONS. |
| | 7. ASSEMBLEY OCCUPANCY, PROVIDE FIRE |
| | RATING INFORMATION ON ALL WALL AND |
| | FLOORS |
| | 8. INFORMATION SUBMITTED IS NOT |
| | SUFFICIENT TO DETERMINE CLASS OF |
| | OCCUPANCY MAY BE LARGE ASSEMBLEY (OVER |
| | ONE THOUSAND PEOPLE). |
| | 9. SHEET AC.2 KITCHEN HOOD DETAIL |
| | PENETRATES THE FIRE RATED WALL SHOWN ON |
| | SHEET A1.1 AND 2, WALL REQUIRES UL |
| | LISTING, DAMPERS ETC. |
| | 10. PROVIDE INFORMATION ON ALL EXTERIOR |
| | GLAZING TO INDICATE CONFORMITY WITH |
| | IMPACT REQUIREMENTS FOR HURRICANE |
| | PROTECTION. |
| | |
| | PLANS LACK MINUMIM INFORMATION REQUIRED |
| | TO BE CONSIDERED FOR PERMIT ISSUANCE. |