2001-06-04 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE SUBMIT A COMPLETE RISER
 DIAGRAM SHOWING SERVICE/ WIRE SIZES ETC
 PLEASE SHOW MEANS OF DISCONNECT AT
 DETACHED STRUCTURE? PANEL?215-5
  
 2)NOTE: PLEASE NOTE FROM FIRST REVIEW
 ON OTHER PERMIT #. PLANS ARE STILL
 SHOWING REQ`D BATH CIRCUIT NOT PER
 210-11-C-3. PLEASE ALSO NOTE THAT AN
 OUTLET PER 210-52D IS REQ`D IN BATH
 AT DETACHED BLDG.
  
 3)NOTE: PLEASE NOTE THAT SMOKE DETECTOR
 IS REQ`D INSDIE MAIN ROOM AT DETACHED
 BLDG. NFPA-72 2-2.1.1.1
  
 4)NOTE: PLEASE CLARIFY AHU AND WATER
 HEATER BEING SHOWN IN SAME LOCATION.
 PLEASE NOTE CLEARENCES PER NEC 110-26
 AND MECH CODE CLEARENCES.
  
 5)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C COND UNIT PER 309.1 OF THE MECH CODE
  
  
 6)NOTE: PLEASE CLARIFY RISER DIAGRAM
 SHOWING MAIN DISCONNECT AND THEN 200A
 PANEL. IS THIS CORRECT OR IS 200A PANEL
 A MCB PANEL. IF DISC IS INLINE THEN
 PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD AFTER FIRST MEANS OF DISCONNECT.
 SIZE PER 250-122.
  
 7)NOTE: PLEASE NOTE THAT PANEL SCHEDULE
 DOES NOT SHOW ANY SUB FEEDS TO DETACHED
 BLDG? PLEASE CLARIFY FEEDS. PLEASE
 SHOW GROUNDING AT DETACHED BLDG.
  
 8)NOTE: PLEASE NOTE THAT GENERAL NOTES
 SHOWN ON PLANS REFERENCE: " ALL WORK TO
 BE PERFORMED IN ACCORDANCE TO MARTIN
 COUNTY" PLEASE NOTE THAT THIS NOTE WOULD
 HVE TO SHOW PALM BEACH COUNTY/CITY OF
 WEST PALM BEACH.
  
 9)NOTE: PLEASE NOTE THAT PLANS THAT ARE
 DONE/DRAWN BY AN ARCH AND/OR ENGINEER
 NEED TO CONTAIN THIER TITLE BLOCK AND
 MUST BE SIGNED AND SEALED BY THAT ARCH/
 ENG. PER F.S AND F.A.C. 61G15-23.002
 481.221 AND 471.025
  
 10)NOTE: PLEASE NOTE THAT A LETTER WAS
 SUBMITTED FOR THE AVAILABLE FAULT CURREN
 T AT FPL`S TRANSFORMER. PLEASE NOTE
 THAT THE PLANS NEED TO SHOW WHAT THE
 ACTUAL AIC RATING OF THE EQUIPMENT/PANEL
 MAIN IS GOING TO BE. PER 110-9/215-5
  
 11)NOTE:PLEASE NOTE THAT TWO COMPLET SET
 S OF PLANS NEED TO BE SUBMITTED.
 PLEASE MAKE NESS CHANGES TO PLANS, WHITE
 OUT ITEMS NOT TO BE PERMITTED AND MAKE
 NEW COPIES. PER 104/104.2/104.2.7 OF
 CITY AND COUNYWIDE ADMIN CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372