| 2001-06-04 00:00:00 | ******************* UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SUBMIT A COMPLETE RISER |
| | DIAGRAM SHOWING SERVICE/ WIRE SIZES ETC |
| | PLEASE SHOW MEANS OF DISCONNECT AT |
| | DETACHED STRUCTURE? PANEL?215-5 |
| | |
| | 2)NOTE: PLEASE NOTE FROM FIRST REVIEW |
| | ON OTHER PERMIT #. PLANS ARE STILL |
| | SHOWING REQ`D BATH CIRCUIT NOT PER |
| | 210-11-C-3. PLEASE ALSO NOTE THAT AN |
| | OUTLET PER 210-52D IS REQ`D IN BATH |
| | AT DETACHED BLDG. |
| | |
| | 3)NOTE: PLEASE NOTE THAT SMOKE DETECTOR |
| | IS REQ`D INSDIE MAIN ROOM AT DETACHED |
| | BLDG. NFPA-72 2-2.1.1.1 |
| | |
| | 4)NOTE: PLEASE CLARIFY AHU AND WATER |
| | HEATER BEING SHOWN IN SAME LOCATION. |
| | PLEASE NOTE CLEARENCES PER NEC 110-26 |
| | AND MECH CODE CLEARENCES. |
| | |
| | 5)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| | A/C COND UNIT PER 309.1 OF THE MECH CODE |
| | |
| | |
| | 6)NOTE: PLEASE CLARIFY RISER DIAGRAM |
| | SHOWING MAIN DISCONNECT AND THEN 200A |
| | PANEL. IS THIS CORRECT OR IS 200A PANEL |
| | A MCB PANEL. IF DISC IS INLINE THEN |
| | PLEASE CLARIFY EQUIPMENT GROUNDING |
| | METHOD AFTER FIRST MEANS OF DISCONNECT. |
| | SIZE PER 250-122. |
| | |
| | 7)NOTE: PLEASE NOTE THAT PANEL SCHEDULE |
| | DOES NOT SHOW ANY SUB FEEDS TO DETACHED |
| | BLDG? PLEASE CLARIFY FEEDS. PLEASE |
| | SHOW GROUNDING AT DETACHED BLDG. |
| | |
| | 8)NOTE: PLEASE NOTE THAT GENERAL NOTES |
| | SHOWN ON PLANS REFERENCE: " ALL WORK TO |
| | BE PERFORMED IN ACCORDANCE TO MARTIN |
| | COUNTY" PLEASE NOTE THAT THIS NOTE WOULD |
| | HVE TO SHOW PALM BEACH COUNTY/CITY OF |
| | WEST PALM BEACH. |
| | |
| | 9)NOTE: PLEASE NOTE THAT PLANS THAT ARE |
| | DONE/DRAWN BY AN ARCH AND/OR ENGINEER |
| | NEED TO CONTAIN THIER TITLE BLOCK AND |
| | MUST BE SIGNED AND SEALED BY THAT ARCH/ |
| | ENG. PER F.S AND F.A.C. 61G15-23.002 |
| | 481.221 AND 471.025 |
| | |
| | 10)NOTE: PLEASE NOTE THAT A LETTER WAS |
| | SUBMITTED FOR THE AVAILABLE FAULT CURREN |
| | T AT FPL`S TRANSFORMER. PLEASE NOTE |
| | THAT THE PLANS NEED TO SHOW WHAT THE |
| | ACTUAL AIC RATING OF THE EQUIPMENT/PANEL |
| | MAIN IS GOING TO BE. PER 110-9/215-5 |
| | |
| | 11)NOTE:PLEASE NOTE THAT TWO COMPLET SET |
| | S OF PLANS NEED TO BE SUBMITTED. |
| | PLEASE MAKE NESS CHANGES TO PLANS, WHITE |
| | OUT ITEMS NOT TO BE PERMITTED AND MAKE |
| | NEW COPIES. PER 104/104.2/104.2.7 OF |
| | CITY AND COUNYWIDE ADMIN CODE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |