Plan Review Notes
Plan Review Notes For Permit 01051544
Permit Number 01051544
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-06-06 00:00:001) THE ABOVEGROUND FUEL TANK IS TO BE
 INSTALLED IN ACCORDANCE WITH NFPA 30,
 THE FLAMMABLE AND COMBUSTIBLE LIQUIDS
 CODE. THE ROOM WHERE THIS STORAGE TANK
 IS TO BE INSTALLED IS TO BE AT LEAST
 TWO HOUR FIRE RATED, BE EQUIPPED WITH A
 FOUR INCH SILL, BE EQUIPPED WITH FIRE
 SPRINKLERS, AND HAVE AT LEAST A B
 LABELED FIRE DOOR WITH A CLOSER. TANK
 IS TO BE LABELED BY UL OR FM.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910