| 2001-06-06 00:00:00 | 1) THE ABOVEGROUND FUEL TANK IS TO BE | | | INSTALLED IN ACCORDANCE WITH NFPA 30, | | | THE FLAMMABLE AND COMBUSTIBLE LIQUIDS | | | CODE. THE ROOM WHERE THIS STORAGE TANK | | | IS TO BE INSTALLED IS TO BE AT LEAST | | | TWO HOUR FIRE RATED, BE EQUIPPED WITH A | | | FOUR INCH SILL, BE EQUIPPED WITH FIRE | | | SPRINKLERS, AND HAVE AT LEAST A B | | | LABELED FIRE DOOR WITH A CLOSER. TANK | | | IS TO BE LABELED BY UL OR FM. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|