| 2001-07-11 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. CITY |
| | AMENDMENTS 104.2.1 |
| | |
| | 4)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - SINGLE HUNG WINDOWS (INFO SUBMITTED IS |
| | NOT ACCEPTABLE) |
| | |
| | 5) PROVIDE (2) PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF ANCHORS |
| | TO BE USED FOR STORM PANELS.(INFORMATION |
| | SUBMITTED IS INCOMPLETE) |
| | |
| | 6) PROVIDE ENERGY CALCULATIONS AND |
| | EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| | AS REQUIRED BY THE 1997 FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILDING |
| | CONSTRUCTION. |
| | |
| | 7) BECAUSE PLANS ARE NOT CERTIFIED BY AN |
| | ARCHITECT OR ENGINEER, THE DESIGN MUST |
| | COMPLY WITH THE 1997 STANDARD FOR |
| | HURRICANE RESISTANT RESIDENTIAL |
| | CONSTRUCTION (SSTD 10-97). |
| | PROVIDE VERTICLE WALL REINFORCEMENT AT |
| | ALL CORNERS. THE SPACING OF VERTICLE |
| | WALL REINFORCEMENT MUST NOT EXCEED 10 FT |
| | VERTICLE REINFORCEMENT IS REQUIRED ON |
| | EACH SIDE OF WINDOW AND DOOR OPENINGS. |
| | PLEASE CORRECT DRAWINGS. |
| | |
| | 8) PROVIDE DETAIL OF CONCRETE SLAB AT |
| | STEP DOWN IN GARAGE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |