Plan Review Notes
Plan Review Notes For Permit 01051483
Permit Number 01051483
Review Stop E
Sequence Number 3
Notes
Date Text
2001-11-13 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT SERVICE HAS CHANGED
 FROM FIRST SET WHICH CONTAINED FUSED
 MAIN DISCONNECT. PLEASE NOTE THAT AIC
 RATINGS NEED TO BE SUBMITTED.
  
 2)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDCUTOR BETWEEN MAIN AND
 200A PANEL AND BETWEEN 200A PANEL AND
 100A PANEL. PLEASE CLARIFY. SIZE PER
 250-122
  
 3)NOTE: PLEASE NOTE THAT PLAN SHOW 3 3/0
 `S BEING INSTALLED IN A 1" CONDUIT?
 PLEASE NOTE THAT THIS DOES NOT MEET
 NEC FOR CONDUIT SIZING AND PIPE FILL.
 PLEASE CLARIFY 3/0`S FOR 100AMPS,??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372