| Plan Review Notes For Permit 01051483 |
| Permit Number |
01051483 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-11-13 00:00:00 | *************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE THAT SERVICE HAS CHANGED | | | FROM FIRST SET WHICH CONTAINED FUSED | | | MAIN DISCONNECT. PLEASE NOTE THAT AIC | | | RATINGS NEED TO BE SUBMITTED. | | | | | | 2)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDCUTOR BETWEEN MAIN AND | | | 200A PANEL AND BETWEEN 200A PANEL AND | | | 100A PANEL. PLEASE CLARIFY. SIZE PER | | | 250-122 | | | | | | 3)NOTE: PLEASE NOTE THAT PLAN SHOW 3 3/0 | | | `S BEING INSTALLED IN A 1" CONDUIT? | | | PLEASE NOTE THAT THIS DOES NOT MEET | | | NEC FOR CONDUIT SIZING AND PIPE FILL. | | | PLEASE CLARIFY 3/0`S FOR 100AMPS,?? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|