| Plan Review Notes For Permit 01051483 |
| Permit Number |
01051483 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-06-04 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SHOW INDICATION ON PANEL. | | | PLANS SHOWS3-4/0`S AND 1-#2 | | | PLEASE NOTE THAT AN EQUIPMNET GROUND IS | | | ONLY INSTALLED AFTER THE FIRST MEANS OF | | | DISCONNECT. PLEASE NOTE THAT PLANS DO | | | NOT SHOW WHAT SIZE THE SERVICE IS GOING | | | TO BE? | | | PLEASE NOTE LOAD CALCUALTIONS SHOWN | | | EXCEED AND DO NOT CORRELATE W/NEC ART | | | 220. | | | PLEASE INDICATE WIRE SIZES ON PANEL | | | SCHEDULE TO CORRELATE W/ LOADS. | | | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 3) PLEASE NOTE MISSING OUTLET FOR A/C | | | EQUIPMENT PER 210-63 OF NEC AND 309.1 | | | MECHANICAL CODE. | | | | | | 4) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | 5)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | SYSTEM PER 250-50. CWP/GROUND ROD. | | | | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|