Plan Review Notes
Plan Review Notes For Permit 01051483
Permit Number 01051483
Review Stop E
Sequence Number 1
Notes
Date Text
2001-06-04 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW INDICATION ON PANEL.
 PLANS SHOWS3-4/0`S AND 1-#2
 PLEASE NOTE THAT AN EQUIPMNET GROUND IS
 ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT. PLEASE NOTE THAT PLANS DO
 NOT SHOW WHAT SIZE THE SERVICE IS GOING
 TO BE?
 PLEASE NOTE LOAD CALCUALTIONS SHOWN
 EXCEED AND DO NOT CORRELATE W/NEC ART
 220.
 PLEASE INDICATE WIRE SIZES ON PANEL
 SCHEDULE TO CORRELATE W/ LOADS.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 4) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 5)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM PER 250-50. CWP/GROUND ROD.
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372