2001-06-23 00:00:00*************BUILDING UNSAT*************
  
 1) STRUCTURE IS LOCATED IN AN A5 FLOOD
 ZONE WITH A BASE FLOOD ELEVATION OF (7)
 FEET. PROVIDE FINISH FLOOR ELEVATION OF
 EXISTING STRUCTURE. CITY CODE REQUIRES
 THAT ALL NEW CONSTRUCTION OR SUBSTANTIAL
 IMPROVEMENT OF ANY EXISTING RESIDENTIAL
 STRUCTURE SHALL HAVE THE LOWEST FLOOR
 ELEVATED TO SIX (6) INCHES ABOVE THE
 BASE FLOOD ELEVATION.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 * ALL EXTERIOR WINDOWS AND DOORS
 - DOUBLE FRENCH DOORS
 - WINDOWS (SINGLE HUNG,CASEMENT,ETC.)
 - SINGLE OUTSWING DOORS (ROOMS 115,119)
  
 5) MISSLE IMPACT PROTECTION IS REQUIRED
 FOR ALL EXTERIOR GLAZING.
 PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 6) PROVIDE DETAIL OF WINDOW AND DOOR
 BUCK CONNECTIONS CAPABLE OF RESISTING
 WINDLOADS.
  
 7) PROVIDE DETAIL INDICATING HOW JAMBS
 ARE TO BE "NARROWED-UP".
  
 8) PROVIDE DETAILS OF NEW EXTERIOR DOOR
 OPENING (ROOM 119) AND WINDOW OPENING
 REPLACING DOOR(ROOM 102).
  
 9) INDICATE LOCATION AND SIZE OF ATTIC
 ACCESS ON PLANS.
  
 10) PROVIDE DETAIL OF OPENING FOR DOUBLE
 DOORS BEING ADDED TO ROOM 102.
  
 11) INDICATE R VALUE FOR WALL AND
 CEILING INSULATION AT COVERED PORCH THAT
 IS BEING ENCLOSED.
  
 12)PROVIDE ENERGY CALCULATIONS AND
 MANUAL J CALCS. AS REQUIRED BY THE 97
 FLORIDA ENERGY CODE.
  
 13) PROVIDE CITY OF WPB DESIGN
 COMPLIANCE FORM FOR NEW EXTERIOR WALLS
 AT ENCLOSED PORCH.
  
 14) PROVIDE TOP AND BOTTOM CONNECTION
 DETAILS FOR NEW EXTERIOR METAL STUD
 WALLS. INDICATE BLOCKING FOR ATTACHMENT
 OF STORM PANELS.
  
 15) PROVIDE ONE BATH ROOM WITH A DOOR
 THAT HAS A 29 INCH CLEAR OPENING (2-8
 DOOR) PER 97 FLORIDA ACCESSIBILITY CODE.
  
 16) 97 SBC SECTION 2504.2 (ASTM C 926)
 REQUIRES EXTERIOR PORTLAND CEMENT
 PLASTER TO HAVE A NOMINAL THICKNESS OF
 7/8". PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202