| 2001-06-23 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | 1) STRUCTURE IS LOCATED IN AN A5 FLOOD |
| | ZONE WITH A BASE FLOOD ELEVATION OF (7) |
| | FEET. PROVIDE FINISH FLOOR ELEVATION OF |
| | EXISTING STRUCTURE. CITY CODE REQUIRES |
| | THAT ALL NEW CONSTRUCTION OR SUBSTANTIAL |
| | IMPROVEMENT OF ANY EXISTING RESIDENTIAL |
| | STRUCTURE SHALL HAVE THE LOWEST FLOOR |
| | ELEVATED TO SIX (6) INCHES ABOVE THE |
| | BASE FLOOD ELEVATION. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 4)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | * ALL EXTERIOR WINDOWS AND DOORS |
| | - DOUBLE FRENCH DOORS |
| | - WINDOWS (SINGLE HUNG,CASEMENT,ETC.) |
| | - SINGLE OUTSWING DOORS (ROOMS 115,119) |
| | |
| | 5) MISSLE IMPACT PROTECTION IS REQUIRED |
| | FOR ALL EXTERIOR GLAZING. |
| | PROVIDE (2) PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF ANCHORS |
| | TO BE USED FOR STORM PANELS. |
| | |
| | 6) PROVIDE DETAIL OF WINDOW AND DOOR |
| | BUCK CONNECTIONS CAPABLE OF RESISTING |
| | WINDLOADS. |
| | |
| | 7) PROVIDE DETAIL INDICATING HOW JAMBS |
| | ARE TO BE "NARROWED-UP". |
| | |
| | 8) PROVIDE DETAILS OF NEW EXTERIOR DOOR |
| | OPENING (ROOM 119) AND WINDOW OPENING |
| | REPLACING DOOR(ROOM 102). |
| | |
| | 9) INDICATE LOCATION AND SIZE OF ATTIC |
| | ACCESS ON PLANS. |
| | |
| | 10) PROVIDE DETAIL OF OPENING FOR DOUBLE |
| | DOORS BEING ADDED TO ROOM 102. |
| | |
| | 11) INDICATE R VALUE FOR WALL AND |
| | CEILING INSULATION AT COVERED PORCH THAT |
| | IS BEING ENCLOSED. |
| | |
| | 12)PROVIDE ENERGY CALCULATIONS AND |
| | MANUAL J CALCS. AS REQUIRED BY THE 97 |
| | FLORIDA ENERGY CODE. |
| | |
| | 13) PROVIDE CITY OF WPB DESIGN |
| | COMPLIANCE FORM FOR NEW EXTERIOR WALLS |
| | AT ENCLOSED PORCH. |
| | |
| | 14) PROVIDE TOP AND BOTTOM CONNECTION |
| | DETAILS FOR NEW EXTERIOR METAL STUD |
| | WALLS. INDICATE BLOCKING FOR ATTACHMENT |
| | OF STORM PANELS. |
| | |
| | 15) PROVIDE ONE BATH ROOM WITH A DOOR |
| | THAT HAS A 29 INCH CLEAR OPENING (2-8 |
| | DOOR) PER 97 FLORIDA ACCESSIBILITY CODE. |
| | |
| | 16) 97 SBC SECTION 2504.2 (ASTM C 926) |
| | REQUIRES EXTERIOR PORTLAND CEMENT |
| | PLASTER TO HAVE A NOMINAL THICKNESS OF |
| | 7/8". PLEASE CORRECT. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |